- 76 -
Figure 6-7 V/F Separation diagram
P4 Group Input Terminal
EV510 series inverter comes standard with seven multi-function digital input terminals
(where S5 can be used as high-speed pulse input terminal), three analog input terminals,
two relay outputs, one optocoupler collector output.
Function code
Name
Factory default
Notes
P4-00
S1 Terminal function selection
1
(
Forward run
)
Standard
P4-01
S2 Terminal function selection
4
(
Moving forward
)
Standard
P4-02
S3 Terminal function selection
9
(
Fault reset
)
Standard
P4-03
S4 Terminal function selection
12
(
Multi-speed 1
)
Standard
P4-04
S5 Terminal function selection
13
Standard
These parameters are used to set the function of the digital multi-function input terminal.
The functions that can
be selected are shown in the following table:
Set
value
Function
Description
0
Non-function
The unused terminal can be set to "no function" to prevent
malfunction.
1
Forward running
(
FWD
)
Through the external terminal to control the inverter forward
and reverse.
2
Reverse
run
(
REV
)
3
Three-wire
operation control
Through this terminal to determine the inverter running mode
is three-wire control mode. For details, please refer to Function
code P4-11 ("terminal command mode").
4
Moving forward
(
FJOG
)
FJOG for the jog forward run, RJOG for the jog reverse run.
Jogging frequency,
Refer to the function codes P8-00, P8-01, P8-02 for the
acceleration / deceleration time.
5
Reversal point