- 66 -
Set range
0
:
operating frequency 1
:
set frequency
This parameter is valid only when the frequency source is digital.
Used to determine the keyboard ▲, ▼ key or terminal UP / DOWN action, the way to amend
the set frequency, that is, the target frequency is based on the operating frequency increase
or decrease, or in the set frequency based on the increase or decrease.
The difference between the two settings, the inverter is in the acceleration and deceleration
process is obvious, that is, if the inverter running frequency and set the frequency is different,
the different options vary widely.
P0-27
The run command is tied to
the main frequency source A
command selection
Factory fault
000
Set range
bit
Operation panel command Bind frequency source
selection
0
:
No bundles 1
:
Numeric setting frequency source
2
:
AI1 3
:
AI2 4
:
AI3
5
:
High speed pulse input setting
(
S5
)
6
:
Multi - step instructions
7
:
simple PLC 8
:
PID 9
:
Communication given
Ten
The terminal command binds the frequency source
selection
(
0
~
9
,
the same as bit
)
hundred
Communication command binding frequency source
selection
(
0
~
9
,
the same as bit
)
Define the combination of three run command channels and nine frequency reference
channels to facilitate synchronous switching.
The meaning of the above frequency reference channel is the same as the main frequency
source A selection P0-03, see the P0-03 function code description.
Different run command channels can be bundled with the same frequency given channel.
When the command source has a bundled frequency source, the set frequency source of
P0-03 ~ P0-07 is no longer active when the command source is valid.
P1 group First motor parameter
Functi
on
code
Function
definition
Factory
default
Set range
parameter
P1-00
Motor 1
type
choose
0
0
Ordinary asynchronous motor
1
Variable
frequency
induction
motor
P1-01
Motor 1
rated
power
Model
determined
0.1kW
~
1000.0kW
P1-00 ~ P1-05 is the motor
nameplate parameter. In the use of
V / F, SVC, FVC control, in order
to
obtain
better
control
performance, the need for motor
parameters of self-learning, and
the correct set of motor nameplate
parameters
P1-02
Motor 1
rated
voltage
Model
determined
1V
~
2000V