- 81 -
OFF
ON
OFF
OFF Multi - step instructions 4
PC-04
OFF
ON
OFF
ON
Multi - step instructions 5
PC-05
OFF
ON
ON
OFF Multi - step instructions 6
PC-06
OFF
ON
ON
ON
Multi - step instructions 7
PC-07
ON
OFF
OFF
OFF Multi - step instructions 8
PC-08
ON
OFF
OFF
ON
Multi - step instructions 9
PC-09
ON
OFF
ON
OFF Multi - step instructions 10
PC-10
ON
OFF
ON
ON Multi - step instructions 11
PC-11
ON
ON
OFF
OFF Multi - step instructions 12
PC-12
ON
ON
OFF
ON Multi - step instructions 13
PC-13
ON
ON
ON
OFF Multi - step instructions 14
PC-14
ON
ON
ON
ON Multi - step instructions 15
PC-15
When the frequency source is selected as multi-step speed, the function code PC-00 ~ PC-
15 100.0%, corresponding to the maximum frequency P0-10.
Multi-segment instructions, in addition to the multi-speed function, can also be used as a
given source for PID or as a voltage source for VF separation control to meet the need to
switch between different set points.
Schedule 2 Acceleration / deceleration time selection terminal
function description
Terminal 2
Terminal 1
Acceleration or
deceleration time
selection
Corresponding
parameters
OFF
OFF
acceleration time 1
P0-17
、
P0-18
OFF
ON
acceleration time 2
P8-03
、
P8-04
ON
OFF
acceleration time 3
P8-05
、
P8-06
ON
ON
acceleration time 4
P8-07
、
P8-08
P4-10
S1~S7 Filter time
Factory
default
0.010s
Set range
0.000s
~
1.000s
Set the software filter time for S1 to S7 terminal status. If the use of occasions, input
terminals susceptible to interference caused by malfunction, this parameter can be increased
to enhance the anti-jamming capability. But the increase in the filter time will cause the S-
terminal response to slow.
This parameter defines four different ways of controlling the drive to run through an
P4-11
The terminal controls the
operating mode
Factory
default
0
Set range
0
:
two wires 1 1
:
two wires 2 2
:
three wires 1
3
:
three wires 2