- 41 -
P6-10
Stop mode
0: Decelerate to stop
1: Coast to stop
0
☆
P6-11
DC injection braking 2 start
frequency
0.00Hz
~
max frequency(P0-10)
0.00Hz
☆
P6-12
DC injection braking 2 delay
time
0.0s
~
100.0s
0.0s
☆
P6-13
DC injection braking 2 level
0%
~
100%
50%
☆
P6-14
DC injection braking 2 active
time
0.0s
~
100.0s
0.0s
☆
P6-15 Braking use ratio
0%
~
100%
100%
☆
P6-18
Catching a spinning motor
current
limit
30%~200%
Model
dependent
☆
P6-21
Demagnetization time
(effective
for SVC)
0.00~5.00s
Model
dependent
☆
P7 Keypad Operation and LED Display
P7-01
JOG default display check
0: JOG is invalid
1: Operation panel command
channel and remote
command channel (terminal
command channel or
communication command
channel) switch
2: Forward and reverse
switching
3: moving forward
4: reverse jog
0
★
Function
Code
Name
Set Range
default
Alteration
P7-02
STOP/RESET key function
0: The STOP / RES key stop
function is valid only during
keyboard operation
1: STOP / RES key shutdown is
active in any mode of operation
1
☆