- 100 -
Setting
Range
0. 0s
~
6500.0s
DSI-200 provides totally four groups of acceleration/deceleration time for selection
(P0-17
、
P0-18 and the above three groups of acceleration/deceleration time).
These four groups of acceleration/deceleration time define are same, please reference
P0-17
、
P0-18 of instruction.
By using the different combination of multi-function digital input terminal S, we can
switch over the selection of 4 groups four groups of acceleration/deceleration time.
Please refer to the relevant instructions in function code P4-01 ~ P4-05.
P8-09
Frequency jump 1
Factory default
0.00Hz
Setting
Range
0.00Hz
~
Maximum frequency
P8-10
Frequency jump 2
Factory default
0.00Hz
Setting
Range
0.00 Hz
~
Maximum frequency
P8-11
Frequency jump band
Factory default
0.00Hz
Setting
Range
0.00
~
Maximum frequency
When the frequency is set in the range of the frequency jump, the actual running
frequency will run at the frequency jump point of the setting frequency nearby. By
setting frequency jump, the inverter can avoid the mechanical resonance of the load.
DSI-200 can be set with two separate frequency jump point. If both are set to 0, the
frequency jump function is disabled. For the principle of jump frequency and jump
frequency range, please refer to figure 6-14.
Figure 6-14 Frequency jump principle
P8-12
Forward/Reverse run
Switch over dead-zone time
Factory default
0.0s