- 129 -
DSI-200 provides five groups of corresponding relationship curve, in which three groups
of curves for the linear relationship (2-point correspondence), 2 groups of 4 points
corresponding to any curve, the user can use P4-13 ~ P4-27 function code and A6 group
function Code to set.
Function code P4-33 is used to set AI1 ~ AI3 three analog input, select which of the five
groups of curves.
AI as the frequency given, the voltage and current input corresponding to the set of 100.0%,
refers to the relative torque digital set A0-03 percentage
4: High-speed pulse setting (S5)
The target torque reference is given by the terminal S5 high speed pulse.
Pulse given signal specifications: voltage range 9V ~ 30V, the frequency range 0kHz ~
100kHz. The pulse reference can only be input from the multi-function input terminal S5
The relationship between the pulse frequency of the S5 terminal input and the
corresponding setting is set by P4-28 to P4-31. The correspondence relationship is a linear
relationship of 2 points, and 100.0% of the pulse input is the relative torque number A0-
03 percentage.
5
:
Communication given
Refers to the target torque postal communication mode given
When a point-to-point communication slave is received and the received data is given as
a torque, use the host to transfer data as the communication reference (see A8 group
description)
Otherwise the host computer through the communication address 0 × 1000 given data, the
data format is -100.00% to 100.00%, 100.00% refers to the relative torque digital set A0-
03 percentage.
A0-05
Torque control forward
maximum frequency
Factory
default
50.00Hz
Set range
0.00Hz
~
max frequency
(
P0-10
)
A0-06
Torque control reverse maximum
frequency
Factory
default
50.00Hz
Set range
0.00Hz
~
max frequency
(
P0-10
)
Used to set the torque control mode, the inverter's forward or reverse maximum operating
frequency.
When the inverter torque control, if the load torque is less than the motor output torque,
the motor speed will continue to rise, in order to prevent the mechanical system, such as
flying accidents, must limit the torque control motor maximum speed.
If you need to achieve dynamic continuous change torque control maximum frequency,
you can use the control of the upper frequency of the way to achieve.
A0-07
Torque control acceleration time
Factory
default
0.00s
Set range
0.00s
~
65000s