- 80 -
Set
value
Function
Description
46
Speed control /
torque control
switching
The frequency converter is switched between torque control
and speed control mode. When the terminal is inactive, the
inverter operates in the mode defined by A0-00 (speed / torque
control mode), and the terminal is switched to another mode.
47
Brake
When the terminal is active, the inverter stops at the fastest
speed, and the current is at the set current limit during the stop.
This function is used to meet the requirements of the inverter as
soon as possible when the system is in a state of emergency.
48
External parking
terminal 2
In any control mode (panel control, terminal control,
communication control), the terminal
So that the inverter deceleration stop, then deceleration time is
fixed to deceleration time 4.
49
Deceleration of
DC braking
When the terminal is active, the inverter first decelerates to the
stop DC brake start frequency, and then switches to
DC braking state.
50
This run time is
cleared
When the terminal is valid, the time of the inverter running
this time is cleared, this function needs to be set
(P8-42) and the run time to reach (P8-53) with the use.
51
Two-wire/ three-
wire switch
Used to switch between two-wire and three-wire controls.
If P4-11 is set to 0 (two-wire type 1), the function of the
terminal is valid, switch to three-wire 1.
If P4-11 is set to 1 (two-wire type 2), the function of the
terminal is valid, switch to three-wire 2.
If P4-11 is set to 2 (three-wire type 1), the function of the
terminal is valid, switch to two-wire 1.
If P4-11 is set to 3 (three-wire type 2), the function of the
terminal is valid, switch to two-wire 2.
52
Reverse
frequency is
disabled
When the terminal is active, the inverter actually set the
frequency to 0 even if the reverse frequency is set.
And the reverse frequency disabled (P8-13) function the same.
Schedule 1 Multi-segment Instruction Function Description
4 multi-stage instruction terminals can be combined into 16 states, 16 of which correspond
to 16 command settings. As shown in Table 1:
K4
K3
K2
K1
Instruction set
Corresponding
parameters
OFF
OFF
OFF
OFF Multi - step instructions 0
PC-00
OFF
OFF
OFF
ON
Multi - step instructions 1
PC-01
OFF
OFF
ON
OFF Multi - step instructions 2
PC-02
OFF
OFF
ON
ON
Multi - step instructions 3
PC-03