- 46 -
Function
Code
Name
Set Range
FACTORY
code
Alteration
P9-00
Motor overload protection
0, 1
1
☆
P9-01
Motor overload protection gain
0.20 to 10.00
1.00
☆
P9-02
Motor overload pre-warning
coefficient
50% to 100%
80%
☆
P9-03
Over
voltage protection gain
0 (no over
voltage stall) to
100
30
☆
P9-04
Over
voltage protection
voltage
650 to 800 V
770 V
☆
P9-07
Detection of short-circuit to
ground
upon power-on
00 to 11
01
☆
P9-08
Braking unit applied voltage
650 to 800 V
760 V
★
P9-09
Auto reset times
0 to 20
0
☆
P9-10
Selection of DO action during
auto
reset
0, 1
0
☆
P9-11
Delay of auto reset
0.1s to 100.0s
1.0s
☆
P9-12
Input phase loss/pre-charge
relay
protection
00 to 11
-
☆
P9-13
Output phase loss protection
00 to 11
01
☆
P9-14
1st fault type
0 to 55
-
●
P9-15
2nd fault type
0 to 55
-
●
P9-16
3rd (latest) fault type
0 to 55
-
●