SYSTEM START-UP AND CONFIGURATION
50
Parker Automation Controller Installation Guide
Configure EtherCAT_Master Node
1.
In the Devices tree, double click the EtherCAT_Master node to bring up the EtherCAT_Master
Configuration dialog.
2.
Ensure that the Autoconfig Master/Slave checkbox is checked.
3.
Change the Distributed Clock Cycletime to the EtherCAT cycle time that you wish to achieve.
(2000 usec in this example). For an EtherCAT network that includes a Compax3, the Distributed
Clock Cycletime should not be lower than 500 usec and must be a multiple of 250 usec. A
Distributed Clock Cycletime of 1000 usec is a reasonable starting point.
4.
Check the Sync Window Monitoring checkbox and set the Sync window to 50.
Configuration of the PACIO (Online Method)
1.
Ensure that you are connected to the PAC (See Connection to the PAC).
2.
Right-
EtherCAT_Master (PAC320 EtherCAT Master)
ee and select
.
Summary of Contents for PAC
Page 11: ...CHAPTER 1 Product Overview...
Page 18: ......
Page 19: ...CHAPTER 2 Installation...
Page 33: ...CHAPTER 3 System Start up and Configuration...
Page 69: ...CHAPTER 4 PACIO Modules...
Page 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Page 155: ...PAC with 400XR series...
Page 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Page 157: ...PAC with 400LXR...
Page 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Page 159: ...CHAPTER 5 Communication Interfaces Optional...
Page 176: ......
Page 177: ...CHAPTER 6 Troubleshooting...
Page 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Page 189: ...APPENDIX A PAC System Specifications...
Page 195: ...APPENDIX B Additional Information...