PACIO-443-06 - AI8 Thermocouple 16 Bit
The PACIO AI8 Thermocouple 16 Bit Module has 8 analog inputs for Thermocouple sensors. It also can
measure mV voltages.
Technical data
PACIO AI8 Thermocouple 16 Bit
Part number
PACIO-443-06
Analog inputs
8
Resolution
16 bit
mV Measuring range
mV: -
µV
Type K measuring range
Type K: -200°C .. +1372°C in 0.1°C
Measurement failure (25°C)
< ± 0.4% regarding range limit
less measurement failure
on demand
Cold junction compensation
Yes
Critical frequency
typical 0.33 Hz
Sampling frequency
> 3.82 Hz (if all channels are enabled)
Connector IO/Power
Plug 18-pole (43-026591-01)
Controller
ASIC ET1200
Baud rate
100 Mbit/s
Power supply
24 VDC -20% +25%
E-Bus load
170mA
Terminals
The PACIO AI8 Thermocouple 16 Bit Module does not need a separate 24V connector. Power is supplied to
the Module through the E-Bus connector. For information on operative earth shielding of analog wire, see
international electromagnetic and emission standards. To reduce radiated emissions, ensure that there is
AI
Summary of Contents for PAC
Page 11: ...CHAPTER 1 Product Overview...
Page 18: ......
Page 19: ...CHAPTER 2 Installation...
Page 33: ...CHAPTER 3 System Start up and Configuration...
Page 69: ...CHAPTER 4 PACIO Modules...
Page 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Page 155: ...PAC with 400XR series...
Page 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Page 157: ...PAC with 400LXR...
Page 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Page 159: ...CHAPTER 5 Communication Interfaces Optional...
Page 176: ......
Page 177: ...CHAPTER 6 Troubleshooting...
Page 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Page 189: ...APPENDIX A PAC System Specifications...
Page 195: ...APPENDIX B Additional Information...