PROFINET Settings
This section is the primary requirement for appending PROFINET communication to existing systems.
Note: Acquire the PROFINET related CoDeSys GSD file for use with CoDeSys product. The file is
called GSDML-V2.1-3S - Smart Software Solutions GmbH-CoDeSys PLC-20120822.xml and by
default, it is installed at this file location:
C:\Program Files(x86)\Parker Hannifin\ParkerAutomationManager\Communication Interface
Files\Profinet GSD Files.
1.
Select PROFINET IO.
2.
Right-click on the PN-IO (X2 Port) of the PLC grid in the upper left.
3.
Click
PROFINET
.
4.
(You will see a network branch appear in the graphical display. This will allow you to add the PAC.
PROFINET device to the configuration).
5.
In the right window listing devices, select the PROFINET
.
6.
Select Additional Field Devices.
7.
Select IO.
8.
Select PAC.
9.
Select PAC PN Device and drag it to the PROFINET network branch you just created.
10.
Double click the new node.
11.
12.
13.
Assign the IP to 192.168.0.1 (note: The IP Address and the Station Name has to match the IP
Address and Device Name on the PROFINET Network within the Siemens Step 7 Software.
14.
Click OK.
15.
Click OK
16.
Expand the PAC PN Device node from the tree on the right
17.
Drag 1 Byte Digital Input to Slot 1 on the green grid on the left
18.
Drag 1 Word Digital Input to Slot 2 on the green grid on the left.
19.
Save the project.
Summary of Contents for PAC
Page 11: ...CHAPTER 1 Product Overview...
Page 18: ......
Page 19: ...CHAPTER 2 Installation...
Page 33: ...CHAPTER 3 System Start up and Configuration...
Page 69: ...CHAPTER 4 PACIO Modules...
Page 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Page 155: ...PAC with 400XR series...
Page 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Page 157: ...PAC with 400LXR...
Page 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Page 159: ...CHAPTER 5 Communication Interfaces Optional...
Page 176: ......
Page 177: ...CHAPTER 6 Troubleshooting...
Page 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Page 189: ...APPENDIX A PAC System Specifications...
Page 195: ...APPENDIX B Additional Information...