Correct (Vertical)
X
Incorrect (Sideways)
X
Incorrect (Horizontal)
X
Incorrect (Upside-down)
Radiated Emissions Guidelines
The PAC and PACIO Modules have been tested to comply with international electromagnetic and emission
standards (IEC/EN61010-1). To reduce radiated emissions, ensure that there is a low impedance earth
connection to the PAC, which can be accomplished by attaching the DIN rail to a suitable Earth ground and
also utilizing Pin-3 on the Controller 24VDC power input connector. This connection must be made with
the shortest possible, heavy gage wire or braided cable. Low-resistance (<0.5 ohms) continuity should be
verified with an ohmmeter for proper grounding. In addition, all communication cables should be shielded
and grounded, preferably only on one end.
Earth Grounding Guidelines
To minimize unwanted electrical interference, select a location away from equipment that produces
intense electrical noise (motor drives, for example). Use good engineering practice and isolate input power
to the unit and separate all data communication cables from AC power lines.
Important: Use the Controller ground terminal (Pin-3 on the 24VDC power
connector) to connect the unit to a suitable ground reference, such as
earth ground or building steel. This ensures the unit is in compliance
with immunity and emissions requirements necessary for proper
operation.
Summary of Contents for PAC
Page 11: ...CHAPTER 1 Product Overview...
Page 18: ......
Page 19: ...CHAPTER 2 Installation...
Page 33: ...CHAPTER 3 System Start up and Configuration...
Page 69: ...CHAPTER 4 PACIO Modules...
Page 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Page 155: ...PAC with 400XR series...
Page 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Page 157: ...PAC with 400LXR...
Page 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Page 159: ...CHAPTER 5 Communication Interfaces Optional...
Page 176: ......
Page 177: ...CHAPTER 6 Troubleshooting...
Page 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Page 189: ...APPENDIX A PAC System Specifications...
Page 195: ...APPENDIX B Additional Information...