PACIO MODULES
112
Parker Automation Controller Installation Guide
Module-Specific Messages
Apart from the Module error messages, the set of messages below contains details about the current
state of the PACIO AO4-VDC/mA 12 Bit Module. These messages are automatically reset when the state
concerned has returned to normal. They are combined into a single "Specific_Error" state of the Module
and output to the IO LED as "Module-
Variable
Data type Explanation
Channel_n_Shortcut
BOOL
Voltage mode: channel n load is < 600
Specific_Error = TRUE
Channel_n_Open
BOOL
Current mode: channel n load is > 500
Specific_Error = TRUE
Channel_n_Overtemp BOOL
Temperature of output driver of channel n is > 140°C (automatic switch-off)
Outputs_Active_Shortcut = TRUE
Undervoltage_24
BOOL
Power supplied to Module is < 19.2V
Outputs_Active_Undervoltage = TRUE
Conversion Time
The PACIO AO4-VDC/mA 12 Bit Module has a set cycle time of 320µs that is not affected by the number of
active channels. The cycle time is the time between receipt of the output values and the start of the D/A
converters.
Summary of Contents for PAC
Page 11: ...CHAPTER 1 Product Overview...
Page 18: ......
Page 19: ...CHAPTER 2 Installation...
Page 33: ...CHAPTER 3 System Start up and Configuration...
Page 69: ...CHAPTER 4 PACIO Modules...
Page 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Page 155: ...PAC with 400XR series...
Page 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Page 157: ...PAC with 400LXR...
Page 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Page 159: ...CHAPTER 5 Communication Interfaces Optional...
Page 176: ......
Page 177: ...CHAPTER 6 Troubleshooting...
Page 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Page 189: ...APPENDIX A PAC System Specifications...
Page 195: ...APPENDIX B Additional Information...