132
Display various fields of positioning actions and flags of the AR area. The
display is the same for both axes, although information for only one axis can
be displayed at a time.
X
Y
AXIS
Designates the axis being displayed: 1: X axis; 2: Y axis.
EXECUTE ADR.
Address of current positioning action, 123 in the figure above. While the sys-
tem is stopped, the address for the next positioning action is displayed.
M-CODE
Displays M code currently being output (89 in the figure above). 00 is dis-
played if no M code is designated.
MULT. FACTOR
Displays the current multiplier (4 in the figure).
SPEED ADR.
Displays the abbreviated current speed address for the speed designated by
the positioning action (56 in the figure).
OVER-RIDE
Displays the override coefficient if in effect (0.7 in the figure).
Displays system and command error codes whenever an error occurs. The
display mode automatically turns to Error Code mode in such cases.
“E0” lights at the axis indicators, followed by an error code display (See
Ap-
pendix D
for the error code list). Only one error code is displayed at a time;
therefore, the system prioritizes multiple errors. After clearing the indicated
error by ERST (error reset), the next error of priority is displayed.
“E” lights at the axis indicators. An error code and related OP code are dis-
played for each axis. The displayed OP code is related to the command er-
ror. Only one error code is displayed at a time; therefore, the system priori-
tizes multiple errors. After clearing the indicated error by ERST (error reset),
the next error of priority is displayed.
X-Axis Status and Y-Axis
Status Modes
Error Code Mode
System Errors
Command Errors
Display Descriptions
Section 9-2