Additional Information
• The default
Input sensitivity setting
is
Standard voltage sensitivity
and this is correct.
Do not set this parameter to
Low voltage sensitivity
. Doing so can cause a system malfunc-
tion when switching to battery mode.
• The UPS Setting Utility can not be used when the Power Attendant Lite Utility is active.
To use the UPS Setting Utility:
1. Right-click the Power Attendant Lite Utility icon and select Agent Stop.
2. Use the UPS Setting Utility.
3. Right-click the Power Attendant Lite Utility icon and select Agent Start.
5-8-2
Connect UPS Using the I/O Connector
The I/O connector of the IPC Application Controller:
• receives the power status of the UPS with the UPS Mode Input when the IPC has a Windows oper-
ating system. For other operating systems this input is not functional.
• indicates the power status of the IPC to the UPS with the Power Status Output.
Additional Information
• A UPS connection using the I/O connector is only possible for a IPC with a Windows operat-
ing system. For all other operating systems use the USB connector to connect the UPS.
Refer to
5-8-1 Connect UPS Using the USB Connector
on page 5-44 for details.
• The IPC does not react automatically to the UPS Mode Input.
A custom software program is required
to shut down the IPC when needed.
UPS Drivers and the required software is available.
• For IPCs with Windows 10 or Windows 7 preinstalled:
• Drivers for the S8BA UPS are pre-installed
• Installation files and manual for the UPS Settings Utility are availabe in the installer directory
D:\OMRON-NY\Installers\
UPS Settings Utility
• For all other IPCs following software can be downloaded:
• Drivers for the S8BA UPS from this OMRON website.
• Installation files and manual for the UPS Settings Utility (Windows only) from this OMRON web-
Precautions for Safe Use
• Always use the recommended uninterruptible power supply (UPS) to prevent data loss and
other system file integrity issues caused by unexpected power interruption.
• Use an Omron S8BA UPS with the correct revision number to prevent improper system shut-
down.
• Correctly perform wiring and setting, and ensure that the shutdown by the UPS can be exe-
cuted.
Follow the steps below to connect the S8BA UPS to the I/O connector of the IPC and to configure it
correctly.
Refer to
on page 5-31 for I/O Connector details.
1
Ensure the revision number of the UPS is correct.
Refer to
on page 2-23 for more information.
5 Installation
5-46
IPC Application Controller User's Manual (I632)
Summary of Contents for AC1-152000
Page 1: ...IPC Application Controller User s Manual I632 E 03...
Page 4: ...Introduction 2 IPC Application Controller User s Manual I632...
Page 32: ...Revision History 30 IPC Application Controller User s Manual I632...
Page 38: ...1 Overview 1 6 IPC Application Controller User s Manual I632...
Page 62: ...2 Hardware 2 24 IPC Application Controller User s Manual I632...
Page 86: ...3 Software 3 24 IPC Application Controller User s Manual I632...
Page 162: ...5 Installation 5 50 IPC Application Controller User s Manual I632...
Page 174: ...6 Operating Procedures 6 12 IPC Application Controller User s Manual I632...
Page 216: ...7 Maintenance 7 42 IPC Application Controller User s Manual I632...
Page 227: ...I Index I 1 IPC Application Controller User s Manual I632 I...