High Temperatures
Use the following cooling methods as required, taking into account the ambient temperature and the
amount of heating inside the panel.
Natural Cooling
Natural cooling relies on natural ventilation through slits in the panel, rather than using cooling devi-
ces such as fans or coolers. When using this method, observe the following points.
• Do not install the IPC at the top of the panel, where hot air tends to stagnate.
• To provide ventilation space above and below the IPC, leave sufficient distance from other devi-
ces, wiring ducts, etc.
• Do not mount the IPC in the wrong direction (e.g., vertically or upside down). Doing so may
cause abnormal heating in the IPC.
• Do not install the IPC directly above any heat-generating equipment, such as heaters or trans-
formers.
• Do not install the IPC in a location exposed to direct sunlight.
Natural Cooling
OMRON
product
OMRON
product
Forced Ventilation
Forced ventilation with a fan in the top of the control cabinet.
Air filter
Fan
Forced Ventilation Method
OMRON
product
OMRON
product
Forced Air Circulation
Forced circulation with a fan inside the closed control cabinet.
5 Installation
5-12
IPC Application Controller User's Manual (I632)
Summary of Contents for AC1-152000
Page 1: ...IPC Application Controller User s Manual I632 E 03...
Page 4: ...Introduction 2 IPC Application Controller User s Manual I632...
Page 32: ...Revision History 30 IPC Application Controller User s Manual I632...
Page 38: ...1 Overview 1 6 IPC Application Controller User s Manual I632...
Page 62: ...2 Hardware 2 24 IPC Application Controller User s Manual I632...
Page 86: ...3 Software 3 24 IPC Application Controller User s Manual I632...
Page 162: ...5 Installation 5 50 IPC Application Controller User s Manual I632...
Page 174: ...6 Operating Procedures 6 12 IPC Application Controller User s Manual I632...
Page 216: ...7 Maintenance 7 42 IPC Application Controller User s Manual I632...
Page 227: ...I Index I 1 IPC Application Controller User s Manual I632 I...