Power Connector Wiring Materials
Use the power supply connector that was supplied to connect the power supply to the IPC Application
Controller.
• Select power supply conductors with consideration to the voltage drop and heat generation for the
cable length at the installation environment.
• Always use twisted wires to minimize the occurrence of electrical disturbance.
• Recommended power supply conductor sizes are provided in the table.
Wire type
Conductor cross-section
Solid conductor
0.5 to 10 mm
2
Flexible conductor
0.5 to 6 mm
2
Flexible conductor, with ferrule and no plastic sleeve
0.5 to 6 mm
2
Flexible conductor, with ferrule and plastic sleeve
0.5 to 4 mm
2
Minimum AWG according to UL/cUL
20
Maximum AWG according to UL/cUL
8
• Power Supply Connector
DC Power Supply
The OMRON S8VK-series power supply is recommended for use with the IPC Application Controller.
Additional Information
• Refer to
on page 2-22 for more information.
• Refer to
4-1-3 Power Consumption Specifications
on page 4-4 for power consumption details.
5 Installation
5-29
IPC Application Controller User's Manual (I632)
5-4
W
ire
5
5-4-3
Wire the Power Connector
Summary of Contents for AC1-152000
Page 1: ...IPC Application Controller User s Manual I632 E 03...
Page 4: ...Introduction 2 IPC Application Controller User s Manual I632...
Page 32: ...Revision History 30 IPC Application Controller User s Manual I632...
Page 38: ...1 Overview 1 6 IPC Application Controller User s Manual I632...
Page 62: ...2 Hardware 2 24 IPC Application Controller User s Manual I632...
Page 86: ...3 Software 3 24 IPC Application Controller User s Manual I632...
Page 162: ...5 Installation 5 50 IPC Application Controller User s Manual I632...
Page 174: ...6 Operating Procedures 6 12 IPC Application Controller User s Manual I632...
Page 216: ...7 Maintenance 7 42 IPC Application Controller User s Manual I632...
Page 227: ...I Index I 1 IPC Application Controller User s Manual I632 I...