• Noise induction may occur if the IPC is installed in a panel that includes high-voltage devices.
Wire and install them as far apart as possible.
• Either install the IPC a minimum of 200 mm away from high-voltage lines or power lines, or place
the high-voltage lines or power lines in metal tubing and completely ground the metal tubing to
100 Ω or less.
Example: Separating an OMRON product from Power Lines
Metal tubing
200 mm
200 mm
High-voltage power panel
Power lines
Power lines
Ground of
100 Ω or less
OMRON
product
OMRON
product
Wiring Ducts
Whenever possible, route the cables and wires through wiring ducts.
Install the wiring ducts so that it is easy to route the wires from the IPC Application Controller di-
rectly into the duct.
Additional Information
Refer to
on page 5-10 for the minimum required distances.
It is convenient to use wiring ducts that have the same depth as the IPC Application Controller.
Duct
Product
Other Precautions
Basic I/O Units have both plus and minus commons, so pay attention to the polarity when wiring.
5 Installation
5-18
IPC Application Controller User's Manual (I632)
Summary of Contents for AC1-152000
Page 1: ...IPC Application Controller User s Manual I632 E 03...
Page 4: ...Introduction 2 IPC Application Controller User s Manual I632...
Page 32: ...Revision History 30 IPC Application Controller User s Manual I632...
Page 38: ...1 Overview 1 6 IPC Application Controller User s Manual I632...
Page 62: ...2 Hardware 2 24 IPC Application Controller User s Manual I632...
Page 86: ...3 Software 3 24 IPC Application Controller User s Manual I632...
Page 162: ...5 Installation 5 50 IPC Application Controller User s Manual I632...
Page 174: ...6 Operating Procedures 6 12 IPC Application Controller User s Manual I632...
Page 216: ...7 Maintenance 7 42 IPC Application Controller User s Manual I632...
Page 227: ...I Index I 1 IPC Application Controller User s Manual I632 I...