19
QUICK SETUP MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
• Spd MENU: SPEEDS AND RAMPS
Parameter Address
Name
Adjustment range
Factory setting
Spd.01
01.06
Maximum reference clamp
0.00 to 60000.00 rpm
1500.00 rpm
Spd.02
01.07
Minimum reference clamp
0.00 to
Spd.01
rpm
0.00 rpm
Spd.03
01.14
Reference selector
Terminal inputs
Analog input 1
Analog input 2
Preset reference
Keypad
Terminal inputs
Spd.04
01.21
Preset ref. 1
+
Spd.01
rpm
0.00 rpm
Spd.05
01.22
Preset ref. 2
+
Spd.01
rpm
0.00 rpm
Spd.06
02.11
Acceleration rate 1
0.1 to 3200.0 s
20.0 s
Spd.07
02.21
Deceleration rate 1
0.1 to 3200.0 s
20.0 s
Spd.08
02.04
Deceleration ramp mode select
Fixed ramp
Automatic ramp
Automatic ramp +
Fixed ramp +
Automatic ramp
If Ctr.02 = Induction motor in vector control mode or PM motor (Servo) in vector control mode:
Spd.09
03.10
Speed loop proportional gain Kp1
0 to 32000
200
Spd.10
03.11
Speed loop integral gain Ki1
0 to 32000
100
• I/O MENU: CUSTOMER INTERFACE
Parameter Address
Name
Adjustment range
Factory setting
I/O.01
07.11
Analog input 2 mode
0-20 mA
20-0 mA
4-20 mA with detection
20-4 mA with detection
4-20 mA without detection
20-4 mA without detection
4-20 mA without
detection
I/O.02
07.15
AI3 signal type
0-20 mA
20-0 mA
4-20 mA with detection
20-4 mA with detection
4-20 mA without detection
20-4 mA without detection
0-10 V
+/-10 V
0-10 V
I/O.03
07.21
AO1 analog output 1 mode
+/-10 V
0-20 mA
4-20 mA
4-20 mA
I/O.04
07.19
AO1 analog output 1 source
Motor speed
Current magnitude
Output power
Active current
Current
magnitude
I/O.05
07.20
AO1 analog output 1 scale
0.000 to 4.000
1.000
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...