35
QUICK SETUP MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
4.3 - Examples of standard configurations
4.3.1 - Quick start of most common applications
• Most common applications include pumps, fans, compressors, mixers, crushers, extruders, …
• The quick start applies to 6 pulse rectifier drives Powerdrive MD2 (MD2MS, MD2CS or MD2S) With or without sensor and with
out brake.
• The quick start considers commissioning the drive using the following default terminal configuration with easy run sequence
adaptation
+10V ref
AI1+
AI1-
AI2+
AI2-
0V
AO1
AI3
+24V ref
DO1
STO-1
DI2
DI3
STO-2
DI5
DI4
+24V ref
1
2
3
4
5
6
8
7
0V
DI1/CTP
10
9
1
2
3
4
5
6
8
7
9
PX1
PX2
PX3
COM-RL1
RL1
COM-RL2
RL2
1
2
3
4
0-10 V
speed reference
4-20 mA
speed reference
4-20 mA current image
Motor PTC (*)
Zero speed
Safe Torque Off/
Drive enable input 1
Reference selection
Reference selection
Safe Torque Off/
Drive enable input 2
Run FWD/Stop
Run REV/Stop
Status relay (2)
Drive healthy (N/O)
Alarm relay
maximum speed (N/O)
• Modification of the Run/Stop control logic
- For «3 wire» control (Jog Run/Stop)
DI4
DI5
+24V ref
7
8
9
Run FWD
Stop
List of parameters to adjust :
Ctr.06 (06.04)
= Run Latched (1),
I/O.10 (08.25)
=
06.39
Stop (DI5 terminal).
- For Run/Stop control with change of direction :
Run/Stop
Change of direction
DI4
DI5
+24V ref
7
9
8
List of parameters to adjust :
Ctr.06 (06.04)
= Run Fwd/Rev (2),
I/O.09 (08.24)
=
06.34
Run/Stop (DI4 terminal),
I/O.10 (08.25)
=
06.33
Fwd/Reverse (DI5 terminal).
For MDX-ENCODER connection, please refer to
Powerdrive MD2 Installation guide, section «Add-on
options»
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...