66
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
5.5.2 - Explanation of parameters in menu 4
04.01
: Current magnitude
Adjustment range : 0.00 to 2.22 x
11.32
(A)
Format: 32 bits
Reading of the rms current in each drive output phase.
This is the result of the vectorial sum of the magnetising current
and the active current.
Note:
Max. drive current = 2.22 x
11.32
.
04.02
: Active current
Adjustment range : ± 2.22 x
11.32
Format: 32 bits
Reading of the active current delivered by the drive.
The active current gives a fairly precise image of the motor
torque between 10 Hz and 50 Hz.
A negative value indicates operation in generator mode with
driving load whereas a positive value indicates operation in
motor mode.
04.03
: Torque demand
Adjustment range : ± 999.9%
Format: 16 bits
Value of the torque demand required by the motor as a % of the
rated motor torque.
04.04
: Active current demand
Adjustment range : ± 999.9%
Format: 16 bits
The current demand is the result of conversion of the torque
reference
04.08
into active current.
04.04
=
04.03
when the drive current limit is not reached and
the motor is not in the defluxing zone.
04.05
: Motoring current limit
Adjustment range : 0.0 to 300.0% (% motor active In)
Factory setting : 150.0% In
Format: 16 bits
Used to set the maximum starting current limit permitted in
motor mode during a maximum time specified by
04.51
.
When the value of
04.05
is less than
04.07
, then
04.05
overrides
04.07
.
04.06
: Regenerating current limit
Adjustment range : 0.0 to 300.0% (% motor active In)
Factory setting : 110.0% In
Format: 16 bits
Used to set the maximum permanent current limit permitted in
generator mode.
04.07
: Symmetric current limit
Adjustment range :0.0 to 300.0% (% motor active In)
Factory setting : 110.0%
Format: 16 bits
Used to set the maximum permanent current limit permitted in
motor mode and in generator mode.
Note:
If
11.31
is set to «Induction motor in open loop mode» (1) and
05.14
is set to «None: Linear U/F law with boost» (2) or
«None: Square U/F law with boost» (5), the only current limit is
then defined by
04.07
.
04.08
: Torque reference
Adjustment range : ±
04.24
(% motor active In)
Factory setting : 0.0% In
Format: 16 bits
Main torque reference when the drive is configured for torque
control.
Give a positive reference for the torque to be applied clockwise
and conversely, a negative reference for the torque to be
applied counter-clockwise.
The maximum value of
04.08
is fixed by
04.24
.
04.09
: Torque offset
Adjustment range : ± 150.0%
Factory setting : 0.0%
Format: 16 bits
04.10
: Torque offset selection
Adjustment range : No (0) or Yes (1)
Factory setting : No (0)
Format: 8 bits
No (0):
The torque reference equals parameter
04.08
.
Yes (1):
The torque reference equals parameter
04.08
plus the torque
offset value
04.09
.
Motor
current limit
Motor operation
t >
04.51
04.05
<
04.07
04.05
Symmetric
current limit
04.07
No
Yes
No
Yes
Generator
current limit
Generator operation
04.06
<
04.07
04.06
Symmetric
current limit
04.07
No
Yes
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...