142
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
16.33
: Timer 4 mode select
Adjustment range : ON timer (0) or OFF timer (1)
Factory setting : ON timer (0)
Format: 8 bits
ON timer (0):
The relay is used for on-delay timing. The output changing to
Enabled (1) is delayed in relation to the input changing to 1.
OFF timer (1):
The relay is used for off-delay timing. The output changing to
Disabled (0) is delayed in relation to the input changing to 0.
Note:
Powering-up of the drive is not taken into account as a transition
of the input; the timer is therefore not activated.
16.34
: Timer 4 unit
Adjustment range : Second (0), Minute (1), Hour (2)
Factory setting : Second (0)
Format: 8 bits
Second (0):
The unit of time for the timer relay is the second.
Minute (1):
The unit of time for the timer relay is the minute.
Hour (2):
The unit of time for the timer relay is the hour.
16.35
: Timer 4 value
Adjustment range : 0.0 to 60.0
Factory setting : 0.0
Format: 16 bits
This parameter is used to set the delay period for timer 4. The
unit depends on the setting of
16.34
.
16.36
to
16.38
:
Not used
16.39
: Timer 4 output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the destination of the output
for timer 4.
Only «bit» type parameters can be assigned to these outputs.
If an unsuitable parameter is addressed, the output will be
frozen at 0.
16.40
: Not used
16.41
: Latch 1 output
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
This parameter indicates the state of the output of latching relay 1.
16.42
: Latch 1 ON source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the enable source for latching
relay 1. A pulse or logic state 1 on the input causes the output
to change to Enabled (1).
Only «bit» type parameters can be assigned to this input. If an
unsuitable parameter is addressed, the input will be frozen at 0.
16.43
: Latch 1 OFF source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the disable source for latching
relay 1. A pulse or logic state 1 on the input causes the output
to change to Disabled (0).
Only «bit» type parameters can be assigned to this input. If an
unsuitable parameter is addressed, the input will be frozen at 0.
16.44
to
16.48
: Not used
16.49
: Latch 1 output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the destination of the output of
latching relay 1.
Only «bit» type parameters can be assigned to this output. If
an unsuitable parameter is addressed, the output will be frozen
at 0.
16.50
: Not used
16.51
: Latch 2 output
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
This parameter indicates the state of the output of latching relay 2.
16.52
: Latch 2 ON source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the enable source for latching
relay 2. A pulse or logic state 1 on the input causes the output
to change to Enabled (1).
Only «bit» type parameters can be assigned to this input. If an
unsuitable parameter is addressed, the input will be frozen at 0.
16.53
: Latch 2 OFF source
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter is used to select the disable source for latching
relay 2. A pulse or logic state 1 on the input causes the output
to change to Disabled (0).
Only «bit» type parameters can be assigned to this input. If an
unsuitable parameter is addressed, the input will be frozen at 0.
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...