84
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
06.21
: Powered-up time: hours, minutes
Adjustment range : 0.00 to 23.59 hrs, min
Format: 16 bits
This parameter records for how many hours and minutes the
drive has been powered up.
After 23.59,
06.21
returns to 0 and
06.20
is incremented by
one day.
06.22
: Run time: years, days
Adjustment range : 0.000 to 9.364 years, days
Format: 16 bits
This parameter records the number of years and days of
operation since the drive was first commissioned.
06.23
: Run time: hours, minutes
Adjustment range : 0.00 to 23.59 hrs, min
Format: 16 bits
This parameter records the number of hours and minutes of
operation since the drive was first commissioned.
After 23.59,
06.23
returns to 0 and
06.22
is incremented by
one day.
06.24
: Energy meter: MW.h
Adjustment range : 0.0 to 999.9 MW.h
Format: 16 bits
This parameter records the drive energy consumption in MW.h.
This meter can be reset to 0 by changing parameter
06.17
to
Enabled (1).
06.25
: Energy meter: kW.h
Adjustment range : 0.00 to 99.99 kW.h
Format: 16 bits
This parameter records the drive energy consumption in kW.h.
This meter can be reset to 0 by changing parameter
06.17
to
Enabled (1).
06.26
to
06.29
:
Not used
06.30
to
06.34
and
06.39
: Sequencing bits
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
The drive’s logic command manager (
06.04
) uses these bits
as inputs rather than referring directly to the terminals. This
enables the user to define the use for each drive terminal
according to the needs of each application. Although these are
read/write type parameters, they are volatile and are not stored
when the drive is powered down. Each time the drive is powered
up they will be reset to Disabled (0).
06.30
: Run forward
06.31
: Jog
06.32
: Run reverse
06.33
: Forward/Reverse
06.34
: Run/Stop
06.39
: Stop
06.35
to
06.38
:
Not used
06.40
and
06.41
:
Not used
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...