159
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
20.15
to
20.19
5 last masked
trips
Adjustment range: 0 to 102 (see
10.20
)
Format: 8 bits
These parameters contain the 5 last drive trips not taken into
account by emergency run mode.
20.15
Indicates the most recent trip
20.19
Indicates the oldest trip
The trips that are disabled in emergency operation are:
No.
Name
Reason for trip
4
Brak. IGBT Braking IGBT transistor overcurrent for
the
POWERDRIVE MD2
5
I
IMBALANCED
Motor current imbalance:
vectorial sum of the 3 motor currents
not zero
8 Drive overload
Ixt
The drive overload level exceeds the
conditions defined in section 1.4.2 of
the installation manual
10 RECTIFIER Th Rectifier heatsink temperature too high
19 Brak. resist. Braking resistor overload I x t:
10.39
=
100%
21
Th IGBT U Overheating of phase U IGBTs
24
Motor PTC
Opening of the DI1/PTC input of the
drive PX1 terminal block or T1/T2
inputs of the MDX-ENCODER option
28
AI2 loss
Loss of the current reference on analog
input AI2
29
AI3 loss
Loss of the current reference on input
AI3
30
COM loss
Loss of communication on the P2
connector serial link
34 Fieldbus loss Disconnection of the fieldbus during
operation or timing error
39 Mains synchro
The rectifier cannot synchronise with
the mains supply
(
POWERDRIVE FX
only)
41
User 1
User trip 1 triggered by state 1 of
10.61
.
42
User 2
User trip 2 triggered by state 1 of
10.63
.
43
User 3
User trip 3 triggered by state 1 of
10.65
.
44
User 4
User trip 4 triggered by state 1 of
10.67
.
45
User 5
User trip 5 triggered by the serial link
10.38
= 45
46
User 6
User trip 6 triggered by the serial link
10.38
= 46
47
User 7
User trip 7 triggered by the serial link
10.38
= 47
48
User 8
User trip 8 triggered by the serial link
10.38
= 48
49
User 9
User trip 9 triggered by the serial link
10.38
= 49
50
User 10
User trip 10 triggered by the serial link
10.38
= 50
58
Th IGBT V • Overheating of phase V IGBTs
• Load too high
59
Th IGBT W • Overheating of phase W IGBTs
• Load too high
66
DO1 over ld The DO1 output load current is >
200 mA
67
Internal
ventilation
The internal ventilation is no longer
working. Contact LEROY-SOMER
Trip only valid for the
POWERDRIVE
FX
50T and 100T)
68
Motor
overcurrent
The current has exceeded the limit
programmed in
05.55
. The load is too
high for the setting.
101 MAINS LOSS Loss of AC supply
102
Rectifier
MD2R
: Regen rectifier trip, signalled by
the serial link to the Regen inverter (see
11.66
).
Powerdrive FX
: Loss of rectifier
synchronisation with the mains.
20.20
to
20.29
: Not used
20.30
: Backspin management
Adjustment range: Disabled (0) or Enabled (1)
Factory setting: Disabled (1)
Format: 8 bits
When this function is enabled, the drive harnesses the potential
energy that may be stored in some very specific load types (eg:
Progressive Cavity Pumps), to extend the possible operating
time without the mains. Depending on the system status when
the mains supply disappears, the drive can therefore operate
for a few minutes rather than a few seconds with just the load’s
kinetic energy.
If the mains supply returns before the time set in
06.62
(adjustable up to 320 seconds, or more than 5 minutes), the
drive reaccelerates the motor up to the reference speed.
Otherwise, a mains loss trip is generated.
20.31
: Backspin speed
Reserved
20.32
: Not used
20.33
: Backspin torque
Reserved
20.34
: Backspin threshold
Reserved
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...