ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
10.13
: Direction commanded
Adjustment range :F orward (0) or Reverse (1)
Format: 8 bits
This parameter indicates Reverse (1) if the pre-ramp reference
is negative.
It indicates Forward (0) if the pre-ramp reference is positive.
10.14
: Direction running
Adjustment range : Forward (0) or Reverse (1)
Format: 8 bits
This parameter indicates Reverse (1) if the post-ramp reference
is negative.
It indicates Forward (0) if the post-ramp reference is positive.
10.15
: Mains loss
Adjustment range : No (0) or Yes (1)
Format: 8 bits
This parameter indicates Yes (1) during loss of the AC mains
power supply. This parameter is only enabled when parameter
06.03
is not set to No detection (0).
10.16
: DC bus undervoltage
Adjustment range : No (0) or Yes (1)
Format: 8 bits
This parameter indicates Yes (1) when the bus voltage level is
too low.
10.17
: Motor overload alarm
Adjustment range : No (0) or Yes (1)
Format: 8 bits
This parameter indicates Yes (1) when parameter
04.19
«Motor thermal state» becomes greater than 100%.
It indicates No (0) when the value is < 95%.
10.18
: Drive overtemperature alarm
Adjustment range : No (0) or Yes (1)
Format: 8 bits
This parameter indicates Yes (1) when one of the temperatures
displayed for
07.51
to
07.55
exceeds 95% of the max
permitted value.
10.19
: Drive general warning
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
Drive general warning = Yes (1) if
10.12
or
10.17
or
10.18
=
«Yes (1)»
or if the Ixt level (
04.21
) exceeds 100%
.
10.20
to
10.29
: Last 10 trips stored
Adjustment range : 0 to 102
Format: 8 bits
Contains the last 10 drive trips.
10.20
: Indicates the most recent trip.
10.29
: Indicates the oldest trip.
The possible trips are:
No. Name
Reason for trip
0
None
1 DC UnderVolt DC bus undervoltage
2
DC over volt DC bus overvoltage
3
Over current Overcurrent at drive output
4
Brak. IGBT
Braking IGBT transistor overcurrent
for the
POWERDRIVE MD2
5 I IMBALANCED
Motor current imbalance:
Vectorial sum of the 3 motor currents
not zero
6 Out Ph. loss of
a motor phase Loss of a motor phase
7
Over speed The speed is greater than (1.3 x
01.06
) or (
01.06
+ 1000 rpm
)
8 Drive overload
Ixt
The drive overload level exceeds the
conditions defined in section 1.4.2 of
the installation manual
9
IGBT U
Protection of phase U IGBTs
10 RECTIFIER Th Rectifier heatsink temperature too high
11
Encoder rot
The measured position does
not vary (only if the MDX-
ENCODER option is present)
13 UVW reversed
The encoder U, V, W signals
are reversed (only if the encoder
option is present)
14 TUNE U Encod During the autotune phase, one of the
U,V,W commutation channels is
missing
15 TUNE V Encod
16 TUNE W Encod
18
Autotun. fail Problem detected during the autotune
phase
19
Brak. resist. Braking resistor overload
I x t:
10.39
= 100%
21
Th IGBT U
• Overheating of phase U IGBTs
• Load too high
24
Motor PTC
Opening of the DI1/PTC input of the
drive PX1 terminal block or T1/T2
inputs of the MDX-ENCODER option
26
24V over ld
Overload on the +24V power supply or
digital outputs
28
AI2 loss
Loss of the current reference on analog
input AI2
29
AI3 loss
Loss of the current reference on input
AI3
30
COM loss
Loss of communication on the P2
connector serial link
31 EEPROM fail. Number of write cycles to EEPROM
exceeded (> 1,000,000)
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...