85
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
06.42
: Control word
Adjustment range :0 to 32767
Factory setting : 0
Format: 16 bits
The control word is used to control the drive via a serial link or
fieldbus:
Control
word bits
06.42
Decimal
conversion
Functions
Equivalent
parameter
0
1
Drive output
06.15
1
2
Run forward
06.30
2
4
Jog
06.31
3
8
Run reverse
06.32
4
16
Forward/Reverse
06.33
5
32
Run/Stop
06.34
6
64
Reserved
7
128
Manual/Auto
8
256
Analog ref./
Preset ref.
01.42
9
512
Reserved
10
1024
Reserved
11
2048
Reserved
12
4096
Reserved
13
8192
Drive reset
10.33
14
16384
Reserved
If the Manual/Auto bit is at 1 and
06.43
= 1, then the drive is
controlled by bits 0 to 6 of control word
06.42
.
If the Manual/Auto bit is at 0 or
06.43
≠
1, then the drive is
controlled by parameters
06.15
,
06.30
,
06.31
,
06.32
,
06.33
,
06.34
,
06.39
.
CAUTION:
For the control word to be taken into account, parameter
06.43
must be at 1.
06.42
should correspond to the binary sum of the
commands to be given to the drive.
Note:
To enable the drive by validating
06.15
(bit 0), the enabling
terminal of the terminal block must previously have been
activated (see explanation of
06.15
).
06.43
: Run/Stop source
Adjustment range :Terminals (0), Fieldbus (1), Not active (2),
LCD keypad (3)
Factory setting : Terminals (0)
Format: 8 bits
Terminals (0):
Commands come from the control terminal block.
Fieldbus (1):
Commands are given by the control word
06.42
.
Not active (2):
Not used.
LCD keypad (3):
Commands come from the connected parameter-setting
interface (MDX-Powerscreen or MDX-KEYPAD).
NB:
Open STO1 and STO2 terminals to modify parameter 06.43.
• When
06.43
changes, control word
06.42
is not
reset. When
06.43
is reset to 1 the drive can restart
if the control word allows this.
06.44
:
Permission to stop cooling fans
Adjustment range: No (0); Yes (1)
• No: parameter
01.11
«Reference enable indicator» is on
«Run» or one of the inverter module temperatures (
07.51
to
07.53
) is higher than 65°C.
• Yes: All the inverter module temperatures are lower than
65°C and parameter 01.11 «Reference enable indicator» is
on «Stop».
06.45
to
06.59
:
Not used
06.60
: Mains undervoltage threshold
Adjustment range : 100 to 600 V
Factory setting : T rating = 300 V, TH rating = 520 V
Format: 16 bits
Used to define the detection level for mains undervoltage.
06.61
: Delay before start
Adjustment range : 0.00 to 327.00 s
Factory setting : 0.00 s
Format: 16 bits
This function is used to delay the motor start-up following the
run command.
06.62
: Delay before mains loss
Adjustment range : 0.00 to 327.00 s
Factory setting : 0.50 s
Format: 16 bits
This parameter is used to set a mains loss time during which
the drive will re-accelerate or decelerate until the motor stops
when
06.03
= Delayed stop (2) (see explanation of
06.03
).
06.63
: Delay before flying restart
Adjustment range : 0.00 to 200.00 s
Factory setting : 2.00 s
Format: 16 bits
Defines the time required for motor demagnetisation before
performing a flying restart procedure (see
06.09
). A setting of
2 seconds is generally sufficient.
If the flying restart does not take place correctly, increase the
value of
06.63
.
This parameter also defines the minimum time between a stop
command and the recognition of a new run command.
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...