100
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
09.27
: Motorised potentiometer down
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
A digital input must be assigned to this parameter for controlling
the motorised potentiometer down function.
09.28
: Motorised potentiometer reset
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
When this parameter is at Enabled (1), the motorised
potentiometer reference is reset to zero.
09.29
to
09.31
: Binary sum inputs
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
Used to modify, using a combination of digital inputs, a parameter
whose selection includes more than 2 possible choices.
09.29
: Binary sum zero input.
09.30
: Binary sum ones input.
09.31
: Binary sum twos input.
09.31
(bit 2)
09.30
(bit 1)
09.29
(bit 0)
Decimal conversion
0
0
0
0
0
0
1
1
0
1
0
2
0
1
1
3
1
0
0
4
1
0
1
5
1
1
0
6
1
1
1
7
09.32
: Binary sum output
Adjustment range : 0 to 39
Format: 8 bits
Used to read the decimal value of the binary sum output.
09.33
: Binary sum destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
Used to define the parameter that the binary sum will control.
Any bit, switch or numerical type parameter can be assigned to
the binary sum.
09.34
: Binary sum output offset
Adjustment range : 0 to 32
Factory setting : 0
Format: 8 bits
Used to add an offset to the binary sum output.
09.35
to
09.51
: Not used
09.52
to
09.54
:
Binary sum 2
sources
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
Used to modify, using a combination of binary parameters, a
parameter whose selection includes more than 2 possible
choices.
09.52
: Binary sum 2 zero source.
09.53
:
Binary sum 2 ones source.
09.54
: Binary sum 2 twos source.
09.54
(bit 2)
09.53
(bit 1)
09.52
(bit 0)
Decimal conversion
0
0
0
0
0
0
1
1
0
1
0
2
0
1
1
3
1
0
0
4
1
0
1
5
1
1
0
6
1
1
1
7
09.55
: Binary sum 2 output offset
Adjustment range : 0 to 32
Factory setting : 0
Format: 8 bits
Used to add an offset to the binary sum 2 output.
09.56
: Binary sum 2 output
Adjustment range : 0 to 39
Format: 8 bits
Used to read the decimal value of binary sum 2 output.
09.57
: Binary sum 2 destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
Used to define the parameter that binary sum 2 output will
control. Any bit, switch or numerical type parameter can be
assigned to the binary sum 2 output.
09.58
and
09.59
: Not used
09.60
: Logic 3 output destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
This parameter defines the internal parameter which will be
assigned by the output of logic function 3.
Only non-protected «bit» type parameters can be addressed.
If an unsuitable parameter is programmed, the destination will
not be taken into account.
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...