23
QUICK SETUP MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
In its factory setting:
- Terminal DI4 preset to FWD.
To change from FWD to REV or vice versa, go via a Stop
command.
Run Fwd/Rev:
Command for Run/Stop via stay-put contact.
In this mode, use DI4 as Run/Stop, and DI5 to give the direction
of rotation.
To do this, configure:
-
I/O.09
=
Run/Stop
(DI4 assignment).
-
I/O.10
=
FWD/Reverse
(DI5 assignment).
Controlled run (no latch) (#):
Command for FWD/Stop and REV/Stop via stay-put contacts.
In its factory setting:
- Terminal DI4 preset to FWD/Stop.
- Terminal DI5 preset to REV/Stop.
On power-up or after a trip reset, if a run command is already
selected, the motor does not start. The Run input (DI4 or DI5)
must be cycled for the command to take effect.
Ctr.07
: Bipolar reference enable
No (#):
All negative references are treated as invalid.
Yes:
Used for changing the direction of rotation by the polarity of the
reference (which may come from the preset references).
0V
DI1/PTC
10
9
PTC motor
to shielding
clamps
(control)
DI4
DI5
+24V ref
FWD
Stop
1
2
3
to shielding
clamps (control)
0V
DI1/PTC
10
9
PTC motor
to shielding
clamps
(control)
DI4
DI5
+24V ref
Run/Stop
Change of
direction
1
3
2
to shielding
clamps (control)
0V
DI1/PTC
10
9
PTC motor
to shielding
clamps
(control)
DI5
DI4
+24V ref
8
7
9
FWD/Stop
REV/Stop
to shielding
clamps (control)
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...