144
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
16.81
: Scan timer PR1 time
Adjustment range : 0 to 9999 s
Factory setting : 0 s
Format: 16 bits
Determines how long the scan timer stays at state 1.
16.82
: Scan timer PR2 time
Adjustment range : 0 to 9999 s
Factory setting : 0 s
Format: 16 bits
Determines how long the scan timer stays at state 2.
16.83
: Scan timer PR3 time
Adjustment range : 0 to 9999 s
Factory setting : 0 s
Format: 16 bits
Determines how long the scan timer stays at state 3.
16.84
: Scan timer PR4 time
Adjustment range : 0 to 9999 s
Factory setting : 0 s
Format: 16 bits
Determines how long the scan timer stays at state 4.
16.85
: Scan timer PR5 time
Adjustment range : 0 to 9999 s
Factory setting : 0 s
Format: 16 bits
Determines how long the scan timer stays at state 5.
16.86
: Scan timer PR6 time
Adjustment range : 0 to 9999 s
Factory setting : 0 s
Format: 16 bits
Determines how long the scan timer stays at state 6.
16.87
:
Scan timer PR7 time
Adjustment range : 0 to 9999 s
Factory setting : 0 s
Format: 16 bits
Determines how long the scan timer stays at state 7.
16.88
: Scan timer PR8 time
Adjustment range : 0 to 9999 s
Factory setting : 0 s
Format: 16 bits
Determines how long the scan timer stays at state 8.
16.89
and
16.90
: Not used
16.91
: Scan timer output
Adjustment range : -127 to +135
Format: 16 bits
Indicates the scan timer state.
16.92
: Scan timer destination
Adjustment range :
00.00
to
21.51
Factory setting :
00.00
Format: 16 bits
Used to define the parameter to which the scan timer state is
addressed.
For example, to scan several speeds, choose
01.15
as
destination.
16.93
: Scan timer reset
Adjustment range : No (0) or Yes (1)
Factory setting : No (0)
Format: 8 bits
When this parameter changes to Yes (1), the scan timer is
reset to 0. In this case, the scan timer returns to state 1. Can be
used to control cycle starting via a digital input.
16.94
: Scan timer mode
Adjustment range : 1st state at start order (0),
Always running (including in stop) (1),
Last state at start order (2),
Factory setting : 1st state at start order (0)
Format: 8 bits
1st state at start order (0):
On the run command, the scan timer is initialised on state 1.
Always running (including in stop) (1):
The scan timer runs permanently, even at standstill (1)
Last state at start order (2):
On the run command, the scan timer reverts to the previous
state.
16.95
: Scan timer offset
Adjustment range : ± 127
Factory setting : 0
Format: 16 bits
Used to add an offset with the value from the scan timer.
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...