111
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
10.67
: User trip 4
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
Disabled (0):
The drive has not tripped.
Enabled (1):
The drive trips, decelerates in freewheel mode and generates
a user trip 4 code.
10.68
: Not used
10.69
: TRIP ENABLE TO OFF
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
This parameter is used to make drive trips active at standstill.
The trips concerned are: IGBT U, V and W, Autotune, I
IMBALANCED, Encoder break, RECTIFIER Th, Motor PTC,
AI2 loss, AI3 loss, Th IGBT U, V and W, Loss of a motor phase,
UVW invert, Internal ventilation.
10.70
to
10.73
: Not used
10.74
: Preload time
Adjustment range : 1 to 15 s
Factory setting : 1 s
Format: 16 bits
Where the drive manages the preloading of capacitors on the
DC bus (
10.75
= No (0)), this parameter sets the DC bus
preload time. Used in the specific case of a rectifier supplying
several inverters.
10.75
: Powered by DC bus
Adjustment range : No (0) or Yes (1)
Factory setting : No (0)
Format: 8 bits
No (0):
The drive is connected to an AC supply. The drive manages the
preloading of capacitors on the DC bus.
Yes (1):
The drive is supplied directly on its DC bus. The preloading of
capacitors on the DC bus must be managed externally.
Note:
• When
10.75
= Yes (1), reading of the rectifier temperature is
disabled («RECTIFIER Th» is no longer active).
•
10.75
must be set to Yes (1) for
POWERDRIVE Regen
(MD2R) units.
10.76
: Preload contactor closed
Adjustment range : No (0) or Yes (1)
Format: 8 bits
No (0):
Short-circuiting of the DC bus preload system is not permitted.
Yes (1):
Short-circuiting for the DC bus preload system may be
permitted.
Note:
10.76
operates with
10.75
at yes (1). The relay switches
when the bus level has reached approximately 90% of its final
value.
10.77
: 4Q rectifier disable
(
POWERDRIVE FX
drive only)
Adjustment range : No (0) or Yes (1)
Factory setting : No (0)
Format: 8 bits
This parameter is used to disable the 4Q rectifier on
POWERDRIVE FX
drives.
No (0):
The rectifier can restore energy to the mains supply.
Yes (1):
The rectifier works as a simple diode bridge.
10.78
and
10.79
: Not used
10.80
: Auto reset type
Adjustment range :Controlled (0) or Automatic (1),
Auto for 1081, 1082, 1083, 1084 (2),
Auto except 1081, 1082, 1083, 1084 (3)
Factory setting : Controlled (0)
Format: 8 bits
Controlled (0):
Trip reset by a Reset command on the terminals or via the
parameter-setting interface.
Automatic (1):
All trips automatically reset.
Auto for 1081, 1082, 1083, 1084 (2):
Selective reset of trips listed in
10.81
,
10.82
,
10.83
and
10.84
.
Auto except 1081, 1082, 1083, 1084 (3):
Selective reset of all trips except trips listed in
10.81
,
10.82
,
10.83
and
10.84
.
NB:
For
MD2R
drives, the regen rectifier automatic reset is only
operational if parameter
18.04
is set to «Synchro x3». The
number of resets is set at 3.
10.81
: Special trip n°1
Adjustment range : 0 to 102
Factory setting : 0
Format: 8 bits
Enter the number of the trip * which should or should not be
reset automatically depending on the setting of
10.80
.
* See the list of trips for parameters
10.20
to
10.29
.
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...