82
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
06.04
: Start stop logic select
Adjustment range : Run no latch (0), Run latched (1),
Run Fwd/Rev (2),
Controlled run no (latch) (3)
Factory setting : Controlled run no (latch) (3)
Format: 8 bits
Used to choose one of 4 Run/Stop command and rotation
direction management modes.
Note:
Modifications to
06.04
must be made with the drive disabled.
Run no latch (0):
Command for FWD/Stop and REV/Stop via stay-put contacts.
In its factory setting:
- Terminal DI4 preset to FWD/Stop.
- Terminal DI5 preset to REV/Stop.
On power-up or after a trip reset, if a Run command is already
selected, the motor starts as soon as the speed reference
appears.
Run latched (1):
Command for Run and Stop via jog contacts.
In this mode, use DI5 to give the Stop command.
To do this, configure:
-
08.25
=
06.39
(DI5 assignment)
-
08.22
=
06.32
(DI2 assignment if necessary)
In its factory setting:
- Terminal DI4 preset to FWD.
To change from FWD to REV or vice versa, go via a stop
command.
Run Fwd/Rev (2):
Command for Run/Stop via stay-put contact.
In this mode, use DI4 as Run/Stop, and DI5 to give the direction
of rotation.
To do this, configure:
-
08.24
=
06.34
(DI4 assignment)
-
08.25
=
06.33
(DI5 assignment)
Controlled run no (latch) (3):
Command for FWD/Stop and REV/Stop via stay-put contacts.
In its factory setting:
- Terminal DI4 preset to FWD/Stop.
- Terminal DI5 preset to REV/Stop.
On power-up or after a trip reset, if a run command is already
selected, the motor does not start. The Run input (DI4 or DI5)
must be cycled for the command to take effect.
06.05
: Not used
06.06
: Injection braking level
Adjustment range : 0.0 to 300.0%
Factory setting : 100.0%
Format: 16 bits
This parameter defines the level of current used for DC injection
braking (see
06.01
and
06.08
).
CAUTION:
For efficient braking, the value of parameter
06.06
should
be 60% minimum.
The values
04.05
,
04.06
and
04.07
can limit the braking
level defined in
06.06
.
06.07
: Injection braking time
Adjustment range : 0.0 to 25.0 s
Factory setting : 1.0 s
Format: 16 bits
This parameter defines the DC injection braking time when
06.01
is at Ramp + DC (2),
Zero speed DC (3) or Timed DC (4).
0V
DI1/PTC
10
9
PTC motor
to shielding
clamps
(control)
DI5
DI4
+24V ref
8
7
9
FWD/Stop
REV/Stop
to shielding
clamps (control)
0V
DI1/PTC
10
9
PTC motor
to shielding
clamps
(control)
DI4
DI5
+24V ref
FWD
Stop
1
2
3
to shielding
clamps (control)
0V
DI1/PTC
10
9
PTC motor
to shielding
clamps
(control)
DI4
DI5
+24V ref
Run/Stop
Change of
direction
1
3
2
to shielding
clamps (control)
0V
DI1/PTC
10
9
PTC motor
to shielding
clamps
(control)
DI5
DI4
+24V ref
8
7
9
FWD/Stop
REV/Stop
to shielding
clamps (control)
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...