116
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
11.27
: Parity type, number of stop bits
Adjustment range :No parity, 2 stop bits (0),
No parity, 1 stop bit (1),
Even parity, 1 stop bit (2),
Odd parity, 1 stop bit (3),
Factory setting : No parity, 2 stop bits (0)
Format: 8 bits
No parity, 2 stop bits (0):
No parity, 2 stop bits.
No parity, 1 stop bit (1):
No parity, 1 stop bit.
Even parity, 1 stop bit (2):
Even parity, 1 stop bit.
Odd parity, 1 stop bit (3):
Odd parity, 1 stop bit.
Note:
This parameter is used only for the MODBUS RTU link of the
drive’s P2 connector. To configure the MODBUS RTU link of
the MDX-MODBUS option, refer to the manual ref. 4580 of the
MDX-MODBUS option.
11.28
: Not used
11.29
: Drive software version
Adjustment range : ± 9.99
Format: 16 bits
Indicates the drive software version.
11.30
: Not used
11.31
: User drive mode
Adjustment range : PM motor in voltage control (0),
Induction motor in open loop mode (1),
Induction motor in vector control mode (2),
PM motor (Servo) in vector control mode (3),
Active rectifier on Main power (4), Active
rectifier for synchronous motor (5), Active
rectifier for induction motor (6), DC/DC
converter (7)
Factory setting
: Induction motor in open loop mode (1)
Format: 8 bits
The operating mode can only be selected when the drive is
stopped.
PM motor in voltage control (0)
Reserved.
Induction motor in open loop mode (1)
:
Asynchronous motor controlled in open loop mode (without
speed feedback). See also parameter
05.14
.
Induction motor in vector control mode (2)
:
Asynchronous motor controlled in closed loop mode with
speed feedback or with the sensorless function (see also
parameter
03.38
).
PM motor (Servo) in vector control mode (3)
:
Permanent magnet motor controlled in closed loop mode with
speed feedback or with the sensorless function (see also
parameter
03.38
).
Active rectifier on Main power (4):
Reversible mode.
Synchronous variable speed Regen (5):
Reversible mode with variable speed synchronous generator.
Asynchronous variable speed Regen (6):
Reversible mode with variable speed asynchronous generator.
DC/DC converter (7):
Reserved
CAUTION:
If the mode is changed with a fieldbus option, reset the
option (Pr
15.32
= ON).
11.32
: Drive current rating
Adjustment range : 1.50 to 3200.00 A
Format: 32 bits
Drive rated current when it is connected to a motor operating
with reduced overload.
11.33
: Drive voltage rating
Adjustment range : 200 to 690 V
Format: 16 bits
This parameter indicates the rated voltage of the drive
according to its rating and
06.10
.
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...