47
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
01.14
: Reference selector
Adjustment range : Terminal inputs (0), Analog input 1 (1),
Analog input 2 (2),
Preset Reference (3),
Keypad (4)
Factory setting : Terminal inputs (0)
Format: 8 bits
Terminal inputs (0):
The speed reference is selected by combining the digital inputs
assigned to parameters
01.41
and
01.42
.
Analog input 1 (1):
The speed reference comes from differential analog input 1
(AI1+, AI1-).
Analog input 2 (2):
The speed reference comes from differential analog input 2
(AI2+, AI2-).
Preset reference (3):
The speed reference comes from the preset references
(RP1 to RP8).
Keypad (4):
The speed reference comes from the
parameter-setting interface (see section 2.2.4).
01.15
: Preset selector
Adjustment range : Terminal inputs (0), Preset reference 1 to
Preset reference 8
Factory setting : Terminal input (0)
Format: 8 bits
This parameter is used to select the preset references.
Terminal input (0):
Used to select the reference by combining the digital inputs
assigned to parameters
01.45
to
01.47
.
Preset reference 1 to
Preset reference 8:
Used to select preset references 1 to 8.
01.16
: Not used
01.17
: Keypad reference
Adjustment range : ±
01.06
Factory setting : 0.00 rpm
Format: 32 bits
Used to set the speed reference value by means of the
parameter-setting interface (see section 2.2.4).
01.18
to
01.20
: Not used
01.21
to
01.28
: Preset ref. 1 to
Preset ref. 8
Adjustment range : ±
01.06
Factory setting : 0.00 rpm
Format: 32 bits
In order,
01.21
to
01.28
are used to define preset references
1 to 8.
01.29
and
01.31
: Skip references 1 and 2
Adjustment range : 0.00 to
01.06
Factory setting : 0.00 rpm
Format: 32 bits
Two skips are available to avoid a machine running at critical
speeds. When one of these parameters is at 0, the
corresponding skip reference is deactivated.
01.30
and
01.32
: Skip reference bands 1 and 2
Adjustment range : 0.00 to 300.00 rpm
Factory setting : 15.00 rpm
Format: 32 bits
Define the skip band around the avoided speed. The total skip
will therefore equal the threshold set ± skip reference band.
When the absolute value of the reference is within the window
determined in this way, the drive will prevent operation in this
zone.
01.33
and
01.34
: Not used
01.35
: Reference in skip zone
Adjustment range : Disabled (0) or Enabled (1)
This parameter is Enabled (1) when the selected reference is
within one of the skip zones.
In this case, the motor speed does not correspond to the
requested reference.
01.36
and
01.37
: Analog references 1 and 2
Adjustment range :
01.07
to
01.06
(
01.10
= 0)
±
01.06
(
01.10
= 1)
Format: 32 bits
The analog inputs assigned to these parameters are
automatically scaled so that 100.0% of the input corresponds
to the maximum reference (
01.06
). Similarly the 0% input
level will correspond to the minimum reference
01.07
or 0
according to
01.10
.
Unipolar mode (
01.10
= 0)
Bipolar mode (
01.10
= 1)
Reference
01.06
01.07
0
100.0
%
Reference
01.06
01.06
- 100.0
+ 100.0
%
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...