17
QUICK SETUP MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
4 - QUICK SETUP MODE
«Quick setup»
contains the parameters most commonly used in standard applications.
Depending on the control type and operating mode selected, the menus offered to the user will adapt in order to make it easier configure
the drive to the driven machine and the application.
STRUCTURE
«Quick setup»
is shown in the form of 5 user menus:
-
BASIC CONTROL OF THE VARIABLE SPEED DRIVE (Ctr)
-
MOTOR NAMEPLATE (Mtr)
,
-
SPEEDS AND RAMPS (Spd)
-
CUSTOMER INTERFACE (I/O)
-
ADDITIONAL SETTINGS (Apl)
Using the parameter-setting interface or MDX-SOFT software, select the
BASIC CONTROL OF THE VARIABLE SPEED DRIVE
(Ctr)
menu, and modify the suggested parameters in order, while keeping the default setting of any unused functions. Depending on
your selections, some menus are automatically adapted (transparent for the user).
Next, set the parameters in the
MOTOR NAMEPLATE (Mtr)
and
SPEEDS AND RAMPS (Spd)
menus.
If the application requires other functions, refer to the
CUSTOMER INTERFACE (I/O)
and
ADDITIONAL SETTINGS (Apl)
menus.
4.1 - List of parameters
• Ctr MENU: BASIC CONTROL OF THE VARIABLE SPEED DRIVE
Parameter Address
Name
Adjustment range
Factory setting
Ctr.01
11.43
Factory settings
Disabled
Centrifugal application
Brake motor application
Other application
Disabled
Ctr.02
11.31
User drive mode
PM motor in voltage control
Induction motor in open loop mode
Induction motor in vector control mode
PM motor (Servo) in vector control mode
Active rectifier on Main power
Active rectifier for synchronous motor
Active rectifier for induction motor
DC/DC converter
Induction motor in
open loop mode
Ctr.03
05.18
Switching frequency
2 - 2.5 - 3 - 3.5 - 4 - 4.5 - 5 - 5.5 - 6 - 6.5 - 7- 8 9
- 10 - 11 - 12 - 13 - 14 - 16 - 18 kHz
FX: 4 kHz
MD2: 3 kHz
Ctr.04
04.07
Symmetric current limit
0.0 to 300.0% (% active In)
110.0%
Ctr.05
06.43
Run/Stop source
Terminals
Fieldbus
Not active
LCD keypad
Terminals
Ctr.06
06.04
Start stop logic select
Run no latch
Run latched
Run Fwd/Rev
Controlled run (no latch)
Controlled run (no
latch)
Ctr.07
01.10
Bipolar reference enable
No or Yes
No
Ctr.08
06.01
Stop mode
Coast
Ramp
Ramp + DC
Zero speed DC
Timed DC
Ramp
Ctr.09
06.09
Catch a spinning motor
Disabled
Enabled
Disabled
Ctr.10
06.03
Mains loss mode
No detection
Full stop
Delayed stop
No detection
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...