46
ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
5.2.2 - Explanation of parameters in menu 1
01.01
: Speed reference selected
Adjustment range : ±
01.06
Format: 32 bits
Indicates the speed reference value.
01.02
: Pre-skip filter reference
Adjustment range : ±
01.06
or
01.07
to
01.06
Format: 32 bits
Speed reference after limiting but before the skips.
01.03
: Pre-ramp reference
Adjustment range :±
01.06
or
01.07
to
01.06
Format: 32 bits
Indicates the speed reference after the skips but before the
acceleration or deceleration ramps.
01.04
: Reference offset
Adjustment range :±
01.06
Factory setting : 0.00 rpm
Format: 32 bits
This reference is added to (positive value) or subtracted from
(negative value) the selected reference if
01.09
is set to «Ref
+
01.04
». It can be used to correct the selected main reference
to obtain an accurate setting.
01.05
: Jog reference
Adjustment range : 0.00 to
01.06
Factory setting : 45.00 rpm
Format: 32 bits
Operating speed when a jog input is configured and
06.31
= 1.
01.06
: Maximum reference clamp
Adjustment range : 0.00 to 60000.00 rpm
Factory setting : 1500.00 rpm
Format: 32 bits
• Before setting the maximum limit, check that the
motor and the driven machine can withstand it.
Maximum speed in both directions of rotation.
01.07
: Minimum reference clamp
Adjustment range : 0.00 to
01.06
Factory setting : 0.00 rpm
Format: 32 bits
In unipolar mode, defines the minimum speed (inactive in bipolar
mode).
CAUTION:
• This parameter is inactive during jog operation.
• If the value of
01.06
is lower than that of
01.07
, the value
of
01.07
is automatically changed to the new value of
01.06
.
01.08
: Not used
01.09
: Reference offset select
Adjustment range : Ref. x
01.38
(0) or Ref. +
01.04
(1)
Factory setting : Ref. x
01.38
(0)
Format: 8 bits
Ref. x
01.38
(0):
A value proportional to this reference is added to the main
reference. The percentage is adjusted using parameter
01.38
(see explanation for
01.38
).
Ref. +
01.04
(1):
A fixed value set in
01.04
is added to the main reference.
01.10
: Bipolar reference enable
Adjustment range : No (0) or Yes (1)
Factory setting : No (0)
Format: 8 bits
No (0):
All negative references are treated as invalid.
Yes (1):
Used for changing the direction of rotation by the polarity of the
reference (which may come from the preset references).
01.11
: Run command
Adjustment range : Stop (0) or Run (1)
Format: 8 bits
Used to control enabling of the run command.
01.12
: Reverse select indicator
Adjustment range : Run forward (0) or Run reverse (1)
Format: 8 bits
Run forward (0):
forward.
Run reverse (1):
reverse.
01.13
: Jog select indicator
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
Disabled (0):
Jog operation disabled.
Enabled (1):
Jog operation enabled.
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...