ADVANCED PARAMETER-SETTING MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
5.9.2 - Explanation of parameters in menu 8
Note:
The sampling period is 2 ms for the digital inputs and
outputs.
08.01
to
08.05
: DI1 to DI5 state
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
These parameters indicate the state of digital inputs DI1 to DI5.
08.06
: DO1 reading
Adjustment range : Disabled (0) or Enabled (1)
Format: 8 bits
08.07
: Output relay 1 state
Adjustment range : Open (0) or Closed (1)
Format: 8 bits
This parameter indicates the state of the output relay.
Open (0):
RL1 open.
Closed (1):
RL1 closed.
08.08
: Output relay 2 state
Adjustment range : Open (0) or Closed (1)
Format: 8 bits
This parameter indicates the state of the output relay.
Open (0):
RL2 open.
Closed (1):
RL2 closed.
08.09
: Safe Torque Off inputs
Adjustment range : 0 to 3
Format: 8 bits
This parameter indicates the state of the «Safe Torque Off»
inputs (at the terminal block), terminals STO1, STO2.
STO2 - STO1: 00 (0):
Drive disabled.
STO2 - STO1: 01 (1):
Tripped.
STO2 - STO1: 10 (2):
Tripped.
STO2 - STO1: 11 (3):
Drive enabled.
08.10
: Not used
08.11
to
08.15
: Digital inputs 1 to 5 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
These parameters are used to invert the state of the digital input.
Disabled (0):
Not inverted.
Enabled (1):
Inverted.
08.16
: Digital output 1 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
This parameter is used to invert the state of output DO1.
Disabled (0):
Not inverted.
Enabled (1):
Inverted.
08.17
:
Output relay 1 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
This parameter is used to invert the state of the relay 1 source.
Disabled (0):
Not inverted.
Enabled (1):
Inverted.
08.18
: Output relay 2 invert
Adjustment range : Disabled (0) or Enabled (1)
Factory setting : Disabled (0)
Format: 8 bits
This parameter is used to invert the state of relay 2.
Disabled (0):
Not inverted.
Enabled (1):
Inverted.
08.19
: Not used
08.20
: Digital I/O read word
Adjustment range : 0 to 511
Format: 16 bits
This parameter is used to determine the state of the I/O with a
single read operation.
Each bit of this word represents the state of parameters
08.01
to
08.09.
Bit
8
7
6
5
4
3
2
1
0
State
08.09 08.08 08.07 08.06 08.05 08.04 08.03 08.02 08.01
E.g.
DI1 = 1 = 2
0
= 1
DI3 = 1 = 2
2
= 4
==>
08.20
= 5
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...