37
QUICK SETUP MODE
Commissioning manual Powerdrive MD2/FX
4617 en - 2017.09 / e
A
1 - Close STO1 and STO2 to enable the drive. HMI displays “ Ready ”
2- Give run command to start Autotune sequence. HMI displays « Autotune » during the sequence and reverts
to « Ready” once completed
3- Open Run command when sequence is completed
Application is ready to be operated
Parameter settings are automatically memorized in drive control board. However it is possible to make a copy in
the HMI using procedure described in paragraph 2.2.3.3
•
Apl.08
(Minimum Speed Threshold) (rpm)
•
Apl.09
(User trip 1) Sets the drive to trip and displays trip
message
•
Apl.10
(Masking time) (s). This masking is used to delay
detection when the drive is enabled in order to
avoid detection on starting.
Main operating parameters
Wish to
trip on minimum
speed
threshold
?
Yes
No
Minimum Speed trip settings
Run Autotune sequence
▪
Spd.01
(Maximum Speed) (rpm)
▪
Spd.06
(Acceleration rate) (s/1000rpm)
▪
Spd.07
(Deceleration rate) (s/1000rpm)
warning:
• This quick start procedure will provide optimum level of performance for most of the applications. However it may happen, in
some few configurations with PM motors, that settings require to be optimized (for example in the case of high load/motor inertia
ratio) some instabilities may be experienced with default settings). For those cases, parameters
Spd.09
&
Spd.10
may be used
to tune the system
• To help supervising the behavior of the motor during tuning, the
MDX-SOFT
PC tool can be used with a laptop connected to the
USB port available on the drive front door (MD2) or on the control board terminal (FX). Use the “Chart” feature of
MDX-SOFT
to
supervise the speed reference (
03.01)
, the motor speed (
05.04
) and the motor current (
04.01
)
Note 1 :
In the event the minimum switching frequency is not available, set the value according to the table below.
- For LSRPM motor, use the informations in the following table
Rated Speed
Minimum Switching Frequency
≤ 1800 rpm
3 KHz
1800 rpm < Rated N ≤3600 rpm
4KHz
3600 rpm < Rated N ≤4500 rpm
5KHz
4500 rpm < Rated N ≤5500 rpm
6KHz
For LSRPM132 et 160 with a rated speed ≥ 2400 rpm, set 8 kHz
- For induction motor, keep the factory setting
Summary of Contents for LEROY-SOMER Powerdrive FX
Page 1: ...4647 en 2017 09 e Powerdrive MD2 FX Commissioning manual R f rence...
Page 41: ...41 QUICK SETUP MODE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 174: ...174 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...
Page 175: ...175 MAINTENANCE Commissioning manual Powerdrive MD2 FX 4617 en 2017 09 e Notes...