FX2N-16CCL-M CC-Link System Master Block
Specification 4
4-3
*1 Dedicated CC-Link cables and dedicated high-performance CC-Link cables cannot be
used at the same time. Only either type of cables are available.
Attach a terminal resistor in accordance with the cable type. (Refer to Section 8.4.)
*2 When an FX
2NC
Series PLC is connected, the interface FX
2NC
-CNV-IF is required.
Connection cable
Dedicated CC-Link cable/Dedicated high-performance CC-Link cable
*1
RAS function
•
Automatic return function
•
Slave station cutoff function
•
Error detection by link special relay/register
Number of times of
parameter registration
to EEPROM
Approximately 10,000 times
Connectable PLC
FX
1N
, FX
2N
(V 2.20 or later), FX
3U
and FX
2NC
(V 2.20 or later)
*2
Series PLC
Number of occupied
I/O points
8 I/O points of FX Series PLC (8 points in total. The ratio between inputs and
outputs is arbitrary.)
Communication with
PLC
By FROM/TO instructions via the buffer memory
Note
•
Scan method: Asynchronous mode
•
Automatic refresh: Not provided
•
Local station function: Not provided
•
Standby master station function: Not provided
•
Intelligent device station connection function: Not provided
•
This master block FX
2N
-16CCL-M and the AS-i maser block FX
2N
-32ASI-
M cannot be connected at the same time.
Operation indication
POWER : Lit while 24V DC is supplied from outside.
L RUN : Lit while communication is normal.
L ERR : Lit when communication error has occurred.
SD
: Lit while data is being transmitted.
RD
: Lit while data is being received.
24V DC external
power supply
Supplied from 24V DC (150 mA) external terminal block.
5V DC internal power
supply
5V DC is self-supplied. 5V DC of PLC is not used.
Accessories
Terminal resistor
•
For standard cable:
110
Ω
, 1/2 W (color cable: brown, brown and brown), 2 cables
•
For high performance cable:
130
Ω
, 1/2 W (color cable: brown, orange and brown), 2 cables
Special block number label
MASS (weight)
0.4kg (0.88lbs)
Table 4.1:
Item
Specification
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......