FX2N-16CCL-M CC-Link System Master Block
Specification 4
4-9
a) Number of connected modules
Set the number of remote station modules (including reserved stations) connected to the
master station.
This is not a station count.
The setting range is "1 to 15 (modules)".
b) Number of retries
Set the number of retries to a remote station with a link data error.
The setting range is "1 to 7 (times)".
If a remote station cannot recover the normal data link after executing the specified
number of retries, the station is regarded as a "data link faulty station".
c) Number of automatic return modules
Set the number of remote station modules that can return to the system during one link
scan.
The setting range is "1 to 10 (modules)".
d) Operation specification for CPU shut down
Specify the data link status when an "operation stop error" occurs in the master station
PLC.
The setting range is "0 (stop)" and "1 (continue)".
e) Reserved station specification
Set remote stations which are included in the number of connected modules but are not
actually connected now so that such stations will not be handled as "data link faulty
stations"
1) When a connected remote station is set as a reserved station, the station cannot
execute any data link at all.
2) Set to ON the bits corresponding to the station numbers to be set as reserved.
For a remote station which occupies 2 or more stations, turn on only the bit for the
station Number set by the module’s station number setting switch.
Numbers 1 to 15 indicate the station numbers in the table below.
Point
The station information (address 20
H
to 2E
H
) for the specified "number of connected
modules" becomes valid.
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
BFM# 10
H
⎯
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......