FX2N-16CCL-M CC-Link System Master Block
Troubleshooting 13
13-9
Error
code
(hex.)
Description
Cause of error (details)
Corrective action
B391
Number of retries
setting error
(parameter)
The number of retries (address 2
H
)
(parameter) is not set inside the
range from 1 to 7.
Set a value inside the range from 1 to
7.
B392
Operation against
CPU down
specification error
(parameter)
The operation specification against
CPU down (address 6
H
) (parameter)
is not set to 0 or 1.
Set 0 or 1.
B394
Number of
automatic return
modules setting
error (parameter)
The number of automatic return
modules (address 3
H
) (parameter) is
not set inside the range from 1 to 10.
Set a value inside the range from 1 to
10.
B396
Station number
overlap error
(parameter)
In the station information (addresses
20
H
to 2E
H
) (parameter), one station
number is specified twice or more.
Use each station number only once.
B397
Station information
setting error
(parameter)
The station information (addresses
20
H
to 2E
H
) (parameter) does not
satisfy the system configuration
condition.
Set the parameters to satisfy the
condition.
B398
Number of
occupied stations
setting error
(parameter)
In the station information (addresses
20
H
to 2E
H
) (parameter), the number
of occupied stations is not set inside
the range from 1 to 4.
Set a value inside the range from 1 to
4.
B399
Number of
connected
modules setting
error (parameter)
The number of connected modules
(address 1
H
) (parameter) is not set
inside the range from 1 to 64.
Set a value inside the specification
range (1 to 15) of the FX Series
master station.
B39B
Reserved station
specification error
(parameter)
In the reserved station specification
(parameter), all stations are set as
reserved ones.
Confirm the reserved station
specification (parameter).
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......