FX2N-16CCL-M CC-Link System Master Block
Data Link Processing Time 6
6-5
6.3.2
Master station
↔
remote device station
1) Master station (RX)
→
remote device station (RX)
[Calculation expression]
SM + LS
×
2 + Remote device station processing time [ms]
SM : Scan time of master station’s sequence program
LS : Link scan time (Refer to Section 6.2.)
[Data flow]
2) Master station (RY)
→
remote device station (RY)
[Calculation expression]
SM + LS
×
3 + Remote device station processing time [ms]
SM : Scan time of master station’s sequence program
LS : Link scan time (Refer to Section 6.2.)
[Data flow]
PLC
FROM
FROM
Buffer memory in master station
(Remote input RX)
Link scan (LS)
Remote device station
RXn (input signal)
PLC
TO
TO
Buffer memory in master station
(Remote output RY)
Link scan (LS)
Remote device station
RYn (output signal)