FX2N-16CCL-M CC-Link System Master Block
Overview 2
2-5
6) Parameter registration to the EEPROM
By registering the parameters to the EEPROM in advance, the parameter settings do not
have to be executed at each startup (power OFF
→
ON) of the master station.
The data stored in the EEPROM remains stored even if the power of the module is turned
off.
7) Data link status setting for a case where an error occurs in the CPU in the master station (PLC)
The data link status can be set (to "stop" or "continue") for a case where an "operation stop
error" such as a PLC program error occurs in the master station.
When an "operation continue error" such as a battery error occurs, the data link continues
without regard to the setting.
8) Status setting of the input data from a data link faulty station
The data input (received) from a data link faulty station can be cleared or kept (in the status
right before an error occurs).
9) Module reset function from a sequence program
When the switch setting is changed or an error occurs in the module, the module can be
reset from a sequence program without resetting the PLC.
(This excludes when the module has a module faulty input (BFM No. A
H
b0 is ON)).
10)RAS function
a) Automatic return function
When a station was disconnected from the link due to power OFF, etc. then returns to
normal status, the station can join the data link again automatically.
b) Link status check
Using the link special relay (SB) and the link special register (SW) in the buffer memory,
the current data link status can be checked.
c) Diagnosis function
Using the switch setting, the hardware and the cable wiring can be checked.
PLC CPU
SETM
TO
SETM
BFM#A
H
b10
BFM#A
H
b8
Parameter
information area
Buffer memory
Master station
E
2
PROM
Internal
memory
The data link is
executed using the
parameters registered
in the internal memory.
➀
➁
➂
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......