*1 Only the bit corresponding to the head station number is set to ON.
Number
Buffer
memory
Name
Description
SW006E
66E
H
Current link scan
time
Stores the current value of the link scan time (unit: 1 ms).
SW006F
66F
H
Minimum link scan
time
Stores the minimum value of the link scan time (unit: 1 ms).
SW0070
670
H
Total number of
stations
Stores the last station number set in parameter.
1 to 15 (stations)
SW0071
671
H
Maximum
communication
station number
Stores the maximum station number (station number set
by the station number setting switch) in the data link.
1 to 15 (stations)
SW0072
672
H
Number of
connected modules
Stores the number of modules (except reserved stations)
in the data link.
1 to 15 (modules)
SW0074
674
H
Reserved station
specification status
*1
Stores the reserved station specification status.
0: Not specified as reserved station
1: Specified as reserved station
Numbers 1 to 15 above indicate station numbers
SW0078
678
H
Error invalid station
specification status
*1
Stores the error invalid station specification status.
0: Not specified as error invalid station
1: Specified as error invalid station
Numbers 1 to 15 above indicate station numbers
SW007C
67C
H
Temporary error
invalid station
specification status
*1
Stores the temporary error invalid station specification
status.
0: Not specified as temporary error invalid station
1: Specified as temporary error invalid station
Numbers 1 to 15 above indicate station numbers
b15 b14 b13 b12
~
b3
b2
b1
b0
SW0074
⎯
15
14
13
~
4
3
2
1
b15 b14 b13 b12
~
b3
b2
b1
b0
SW0078
⎯
15
14
13
~
4
3
2
1
b15 b14 b13 b12
~
b3
b2
b1
b0
SW007C
⎯
15
14
13
~
4
3
2
1
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......