FX2N-16CCL-M CC-Link System Master Block
Communication between Master Station and Remote I/O Stations 10
10-8
10.3.2
Confirmation of operation by program
Using a sequence program, make sure that data link is normally proceeding.
➀
For example, when the input X00 in the remote I/O station AJ65BTB1-16D (station No. 1) is
set to ON, the output Y000 in the master station turns ON.
➁
When the input X000 in the master station is set to ON, the output Y00 in the remote I/O
station AJ65BTB1-16T (station No. 2) turns ON.
Terminal
resistor
Terminal
resistor
Remote I/O station
(station No. 1)
Remote I/O station
(station No. 2)
Remote I/O station
(station No. 3)
I/O module
AJ65BTB1-16DT
Output module
AJ65BTB1-16T
Input module
AJ65BTB1-16D
CC-Link master block
FX
2N
-16CCL-M
X000
ON
Y000
ON
➀
➁
X00
ON
➀
Y00
ON
➁
FX
1N
/FX
2N
/FX
3U
/FX
2NC
Series PLC
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......