FX2N-16CCL-M CC-Link System Master Block
Data Link Procedure 8
8-5
Table 8.1:
Number
Name
Description
1)
LED indicators 1
LED
name
Description
LED status
Normal
Error
RUN
ON : Module is normal.
OFF : Watchdog time error has occurred.
ON
OFF
ERR.
Indicates the communication status with the
stations set in parameter.
ON
: Communication error has
occurred in all stations.
Flashing : Communication error has
occurred in some stations.
OFF
ON or
flashing
MST
ON : Set as the master station
ON
OFF
TEST1
Test result indication
OFF except during
test
TEST2
Test result indication
L RUN
ON : Data link is being executed
(host station).
ON
OFF
L ERR.
ON
: Communication error has
occurred
(host station).
Flashing : The settings of the switches (4)
to (7) are changed while the
power is ON.
OFF
ON or
flashing
2)
Power indictor
POWER ON : 24V DC is supplied from the outside.
ON
OFF
3)
LED indicators 2
E
R
R
O
R
SW
ON : Switch setting error has occurred.
OFF
ON
M/S
ON : The master station is already present
in the same line.
OFF
ON
PRM ON : Parameter setting error has occurred.
OFF
ON
TIME
ON : Data link watchdog timer is actuated
(error in all stations).
OFF
ON
LINE
ON : The cable is broken or the
transmission route is affected by
noise, etc.
OFF
ON
SD
ON : Data is being transmitted.
ON
OFF
RD
ON : Data is being received.
ON
OFF
4)
Station number
setting switch
Sets the station number of the module. (Default setting at shipment: 00)
<Setting range>
00 (because the FX
2N
-16CCL-M is dedicated to the master station)
If "65" or larger number is set, the "SW" and "L ERR." LED indicators turn
ON.
RUN
ERR.
MST
TEST 1
TEST 2
L RUN
L ERR
SW
M/S
PRM
TIME
LINE
SD
RD
E
R
R
O
R
STATION NO.
×
10
×
1
1
2 3 4
5
6
78
9
0
1
2 3 4
5
6
78
9
0
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......