FX2N-16CCL-M CC-Link System Master Block
Programming 9
9-10
9.3.2
Link special register (SW)
*1 Sets to ON only the bit corresponding to the head station number
Table 9.2:
Number
Buffer
memory
Name
Description
SW0003
603
H
Specification of
multiple temporary
error invalid stations
Selects whether or not to specify two or more temporary
error invalid stations.
00: Specifies two or more stations stored in SW0004.
01 to 15 : Specifies a single station whose station
number is 1 to 15.
* The number indicates the station number of a
temporary error invalid station.
SW0004
604
H
Temporary error
invalid station
specification
*1
Specifies temporary error invalid stations.
0: Does not specify as temporary error invalid station.
1: Specifies as temporary error invalid station.
Numbers 1 to 15 above indicate station numbers
SW0008
608
H
Line test station
setting
Sets the stations to be subject to the line test.
0 : Entire system (The line test will be executed to all
stations.)
01 to 15 : Station to be subject to the line test.
Default : 0
SW0020
620
H
Module status
Indicates the module status.
0 : Normal
Other than 0 : Error code (Refer to Section 13.3.)
SW0041
641
H
Result of data link
restart
Stores the execution result of data link restart
specification by SB0000.
0 : Normal
Other than 0 : Error code (Refer to Section 13.3.)
SW0045
645
H
Result of data link
stop
Stores the execution result of data link stop specification
by SB0002.
0 : Normal
Other than 0 : Error code (Refer to Section 13.3.)
SW0049
649
H
Result of request for
temporary error
invalid stations
Stores the execution result of request for temporary error
invalid stations by SB0004.
0 : Normal
Other than 0 : Error code (Refer to Section 13.3.)
SW004B
64B
H
Result of request for
cancel of temporary
error invalid stations
Stores the execution result of request for cancel of
temporary error invalid stations by SB0005.
0 : Normal
Other than 0 : Error code (Refer to Section 13.3.)
SW004D
64D
H
Result of request for
line test
Stores the execution result of request for line test by
SB0008.
0 : Normal
Other than 0 : Error code (Refer to Section 13.3.)
b15 b14 b13 b12
~
b3
b2
b1
b0
SW0004
⎯
15
14
13
~
4
3
2
1
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......