Parameter Setting 7
7-1
7.
Parameter Setting
This chapter describes the parameter setting required to execute data link in the CC-Link
system.
7.1
Procedure from Parameter Setting to Data Link Startup
This section describes the flow from parameter setting to data link startup.
7.1.1
Relationship among buffer memory, EEPROM and internal memory
This section describes the relationship among the buffer memory, the EEPROM and the
internal memory in the master station.
1) Buffer memory
This is a temporary storage area to write the parameter information to the EEPROM or the
internal memory.
Write the parameter information to the buffer memory using a sequence program.
(When the power of the master block is turned off, the parameter information is erased.)
2) EEPROM
Only by setting to ON the write request for data link startup by EEPROM parameters
(BFM#A
H
b8), data link can be started up.
This eliminates the necessity to write parameters to the buffer memory every time the
master station starts up.
However, the parameter should be registered in advance to the EEPROM by the write
request for parameter registration to EEPROM (BFM#A
H
b10).
Even when the power of the master block is turned off, the parameter information stored in
the EEPROM remains stored.
The registration limit to the EEPROM is 10,000 times.
3) Internal memory
Data link is executed using the parameter information stored in the internal memory.
When the power of the master block is turned off, the parameter information is erased.
Parameter
information area
Buffer memory
The parameter
information is
erased when the
power is turned off.
E
2
PROM
Internal memory
Data link is
executed using this
parameter
information.
M
SET
BFM#A
H
b10
TO
M
SET
BFM#A
H
b8
M
SET
BFM#A
H
b6
PLC
Master station
The parameter
information
remains stored
even when the
power is turned off.
FX2N-16CCL-M CC-Link System Master Block
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......