Functions 5
5-18
5.9
Module Reset Function from Sequence Program
This function resets a module from a sequence program without resetting the PLC or the
master block when the switch settings are changed or an error occurs in the master block.
However, reset is disabled when there is an read module error (when the BFM#A
H
b0 is
ON).
The figure below shows a program example for module reset.
Point
Because the PLC is not initialized, operations of other modules are not affected at
all.
Remarks
Change from the mode 0 or the mode 2 to the test mode cannot be executed by the
write request for module reset (BFM#A
H
b4).
For such a change, turn off the power, then turn it on again.
M8000
FROM
K0
HA
K4M0
K1
Reads from BFM#A
H
.
BFM#A
H
→
M15 to M0
RUN monitor
Reset command
M4 (module reset acceptance completion)
M8000
RUN monitor
SET
M24
RST
M24
TO
K0
HA
K4M20
K1
Sets to ON the write request for
module reset.
Writes to BFM#A
H
.
M35 to M20
→
BFM#A
H
Sets to OFF the write request for
module reset.
Summary of Contents for FX2N-16CCL-M
Page 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Page 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Page 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Page 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Page 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Page 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Page 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Page 193: ......