FX2N-16CCL-M CC-Link System Master Block
Data Link Procedure 8
8-2
WIRING PRECAUTIONS
• Perform Class D grounding (100
Ω
or less) with a wire of 2 mm
2
or more to the grounding
terminal in the PLC main unit. However, never perform common grounding with a high
voltage system.
• Do not bundle control cables and communication cables with the main circuit and power
cables. Keep control cables and communication cables at least 100 mm away from the main
circuit and power cables.
Otherwise, electric noise may cause a malfunction.
PLC
Another
equipment
PLC
Another
equipment
PLC
Another
equipment
Common grounding
(allowed)
Common grounding
(not allowed)
Dedicated grounding
(best)