FX2N-16CCL-M CC-Link System Master Block
Data Link Processing Time 6
6-4
6.3
Transmission Delay Time
This section describes the transmission delay time (time required for data transmission).
6.3.1
Master station
↔
remote I/O station
1) Master station (RX)
←
remote I/O station (input)
[Calculation expression]
SM + LS
×
2 + Remote I/O station response time [ms]
SM : Scan time of master station’s sequence program
LS : Link scan time (Refer to Section 6.2.)
[Data flow]
2) Master station (RY)
→
remote I/O station (output)
[Calculation expression]
SM + LS
×
3 + Remote I/O station response time [ms]
SM : Scan time of master station’s sequence program
LS : Link scan time (Refer to Section 6.2.)
[Data flow]
PLC
FROM
FROM
Buffer memory in master station
(Remote input RX)
Link scan (LS)
Remote I/O station
PLC
TO
TO
Buffer memory in master station
(Remote output RY)
Link scan (LS)
Remote I/O station